Adaptive fan control

Blasinski, Petr; Rubina, Aleš; Rubinová, Olga; Jůza, Štěpán

Abstract

The paper presents the possibility of management the fan performance in dependence on CO2 concentration. A mathematical calculation is made from the prediction of the electric energy consumption for a variant control algorithm. The most advantageous algorithm is programmed into the actual fan control system, and its power consumption is shown in graph. Finally, the saving of the adaptive control is compared to the classical control over time. To program the control algorithm, the CO2 mass balance equation is used. The equation depends on the input values, namely the number of CO2 sources, the room volume and the supply air. Due to the infinitely variable of fan control, it is possible to adjust the power setting depending on the expected development of the logarithmic rise of CO2 concentration in the room. This prediction is programmed with the Visual Basic code and program code can be used to the Arduino control unit, which controls the EC fan power with a 0-10 V signal. Although significant savings over a short period of time can not be expected, the ventilation system where the fan runs for a significant part of the year will be substantial. Therefore, the result will be presented by graphical diagrams of different ways of controlling the fan per year of operation.

Full text

Content from this work may be used under the terms of theCreativeCommonsAttribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by IOP Publishing Ltd SEED 2019 IOP Conf. Series: Earth and Environmental Science 642 (2021) 012008 IOP Publishing doi:10.1088/1755-1315/642/1/012008 1 Adaptive fan control Petr Blasinski1,*, Aleš Rubina1, Olga Rubinová1, Štěpán Jůza1 1Brno University of Technology, Faculty of Civil Engineering, Veveří 331/95, 602 00 Brno, Czech Republic *E-mail: Petr.Blasinsk[email protected] Abstract. The paper presents the possibility of management the fan performance in dependence on CO₂ concentration. A mathematical calculation is made from the prediction of the electric energy consumption for a variant control algorithm. The most advantageous algorithm is programmed into the actual fan control system, and its power consumption is shown in graph. Finally, the saving of the adaptive control is compared to the classical control over time. To program the control algorithm, the CO₂ mass balance equation is used. The equation depends on the input values, namely the number of CO₂ sources, the room volume and the supply air. Due to the infinitely variable of fan control, it is possible to adjust the power setting depending on the expected development of the logarithmic rise of CO₂ concentration in the room. This prediction is programmed with the Visual Basic code and program code can be used to the Arduino control unit, which controls the EC fan power with a 0-10 V signal. Although significant savings over a short period of time can not be expected, the ventilation system where the fan runs for a significant part of the year will be substantial. Therefore, the result will be presented by graphical diagrams of different ways of controlling the fan per year of operation. 1. Introduction Energy consumption during ventilation operation can be significantly reduced by designing efficient HVAC systems with low fan input. The efficiency of ventilation systems is generally relatively low so far, but the savings potential can be increased by a suitable fan control algorithm. The energy consumption of fans can be significantly reduced by following these three steps. The first step is to reasonably dimension the air exchange intensity by reducing as much air as possible and by using efficient air distribution. Efficient air ducts reduce unnecessary over-ventilation due to the use of air-tight ducts, respect for air flow principles and air flow control. Perhaps the most important thing is to reduce the flow resistance and therefore the fan pressure. This is achievable through aerodynamic piping design (including optimum engine room and riser placement to reduce piping length), more generous dimensioning of piping elements, and increased unit size, but without overall oversizing of the HVAC system. It is necessary to optimize the efficiency of the HVAC system (including fan, drive, motor and variable speed drive, to minimize overall losses in ensuring the necessary air flow and pressure conditions). Oversizing should be avoided, as the efficiency of the fan may decrease significantly if the combination of air flow and delivery pressure is not close to the combination achieving the highest SEED 2019 IOP Conf. Series: Earth and Environmental Science 642 (2021) 012008 IOP Publishing doi:10.1088/1755-1315/642/1/012008 2 efficiency. The efficiency of the motor and drive can also drop significantly at low loads. Therefore, oversizing and variable loads are key factors affecting system efficiency. These three measures are much more important in climates where there is a need to heat or cool than some use of natural driving forces. The article focuses on the first of these points, especially on the control of fan operation. 2. Description of the room model and the selected fan type In the mathematical model, the calculation of ventilation is made for the school classroom. Dimensional characteristics are room width 21.0 m, room length 13.3 m, room height 3.8 m. Room volume is 1061 m3, maximum number of persons is forty. To introduce a variable rate of people in the room, the percentage of people was distributed according to the distribution shown on Figure 1. Figure 1. Percentage distribution of people in the room Natural ventilation of the room by windows infiltration was considered. However, this part of the ventilation component is minimal. A radial fan is considered. Traditionally, the impeller is embedded in a spiral casing that provides an energy efficient conversion of the kinetic energy of the flowing air into a pressurized air. In connection with the application of new EC motors, we can observe the expansion of radial fans with “free impeller”, where the spiral box is replaced directly by the air-handling unit chamber. This modification of the fan-motor set significantly reduces and cheaper, but at the cost of aerodynamic properties. The air flow in the spiral housing is shown on Figure 2. [1] Figure 2. Air flow through radial fan with spiral housing [1] 3. Computational model and description of variants The computational model of the room is considered as an analytical model. [2] 𝑉󰇗∙𝑘𝑒𝑑𝜏+𝑀󰇗𝑠𝑑𝜏−𝑉󰇗∙𝑘𝑖𝑑𝜏=𝑂𝑑𝑘𝑖 (1) Where: 𝑉󰇗∙𝑘𝑒𝑑𝜏 is the mass of the pollutant introduced into the room by the air required for ventilation over time dτ 𝑀󰇗𝑠𝑑𝜏 is the mass of the pollutant from the source in the room over time dτ impeller SEED 2019 IOP Conf. Series: Earth and Environmental Science 642 (2021) 012008 IOP Publishing doi:10.1088/1755-1315/642/1/012008 3 𝑉󰇗∙𝑘𝑖𝑑𝜏 is the mass of the pollutant taken from the room by the air required for ventilation over time dτ 𝑂𝑑𝑘𝑖 is the weight gain of the pollutant in the room air 𝑘𝑖𝑛𝑡𝑖=𝑘𝑒𝑥𝑡 +(𝑘𝑖𝑛𝑡𝑖−1 −𝑘𝑒𝑥𝑡)∙exp(−𝑉(𝑖−1)∙∆𝜏𝑖 𝑂)+( 𝑀𝑠𝑖 𝑉(𝑖−1))∙(1−exp(−𝑉(𝑖−1)∙∆𝜏𝑖 𝑂)) (2) Where: 𝑘𝑒𝑥𝑡 is outdoor CO₂ concentration 𝑘𝑖𝑛𝑡𝑖 is maximum CO₂ concentration 𝑀󰇗𝑠 is the mass of the pollutant (CO₂) 𝑉(𝑖−1) is forced ventilation (estimated) 𝑂 is the volume of the room ∆τ is calculation time interval Description of individual fan control variants: Variant 1 - minimum fan start interval is 5 min, the fan is switched on at a measured of CO₂ concentration 900 ppm, type of regulation: on / off. Variant 2 - minimum fan start interval is 30 min, the fan is switched on at a measured of CO₂ concentration 900 ppm, type of regulation: on / off Variant 3 - minimum fan start interval is 5 min, the fan is switched on at a measured of CO₂ concentration 900 ppm and switched off only after reaching a CO₂ concentration of 600 ppm, type of regulation: on / off Variant 4 - minimum fan start interval is 5 min, the fan is switched on at a measured of CO₂ concentration 900 ppm and switched off only after reaching a CO₂ concentration of 600 ppm, type of control: stepping (2 fans regulated on / off) Variant 5 - minimum fan start interval is 5 min, the fan is switched on at a measured of CO₂ concentration 900 ppm and only switched off after reaching a CO₂ concentration of 600 ppm, type of regulation: continuous regulation (air flow is controlled linearly according to CO₂ concentration) Variant 6 - minimum fan start interval is 5 min, the fan is switched on at a measured of CO₂ concentration 900 ppm and turns off after reaching a CO₂ concentration of 600 ppm, type of regulation: continuous regulation (air flow is controlled quadratically - convex according to CO₂ concentration) Variant 7 - minimum fan start interval is 5 min, the fan is switched on at a measured of CO₂ concentration 900 ppm and switched off only after reaching a CO₂ concentration of 600 ppm, type of regulation: continuous regulation (air flow is controlled quadratically - concave according to CO₂ concentration) Figure 3. Graphical dependence of fan power control, from left: linear, quadratic - convex, quadratic – concave SEED 2019 IOP Conf. Series: Earth and Environmental Science 642 (2021) 012008 IOP Publishing doi:10.1088/1755-1315/642/1/012008 4 Figure 3 shows the air flow dependencies on CO2 concentration which are used in the calculation of variants 5, 6 and 7. These dependencies affect the start-up of the fan operation and they significantly influence the fan power output. 4. Results The results are presented by using the graphs. On figure 4 there is a graph of increasing CO₂ concentration the fan operation variant 1. Figure 4. Graphical representation of the course of CO₂ concentration reduction, with the fan operation variant 1 When the concentration rises above 900 ppm, a fan is triggered (light blue color). The results shown represent an on/off control variant with a minimum operating interval of 5 min. The graph shows frequent switching of ventilation. Graph on the figure 5 represents the adaptation of the fan power to the quadratic dependence on the CO₂ concentration. The ventilator is operating continuously, but the power adapts to the actual CO₂ concentration. Figure 5. Graphical representation of the course of CO₂ concentration reduction, with the fan operation variant 7 On the figure 6 there are results for the cumulative CO₂ concentrations for the fan control variants 1-7. SEED 2019 IOP Conf. Series: Earth and Environmental Science 642 (2021) 012008 IOP Publishing doi:10.1088/1755-1315/642/1/012008 5 Figure 6. Graphical representation of the course of CO₂ concentration reduction, with the fan operation variant 1-7 The overall results of the fan operation per day, month and year according to the model above are shown in the figure 7. Figure 7. Fan operating time for operating variants 1-7 The economic evaluation is shown on figure 8. The price of 0.17 EUR for kWh of electricity was considered in the preparation of this chart. The power input of the fans was determined from the characteristics of the fan manufacturer. SEED 2019 IOP Conf. Series: Earth and Environmental Science 642 (2021) 012008 IOP Publishing doi:10.1088/1755-1315/642/1/012008 6 Figure 8. Price per year of fan operation for each variant and percentage savings compared to the most expensive variant 5. Conclusion The results show that the greatest savings are achieved in variant 6, which is the control of the fan according to the quadratic dependence in the convex shape. However, it should be added that this method was the only method to exceed the recommended CO₂ concentration. This is because the fan's start-up is very slow in nature and the fan starts to run at higher CO₂ concentrations at higher power. The compromise between performance, savings and CO₂ concentration results from variant 7, fan control according to quadratic dependence in concave shape. In this case, the ventilator can effectively ventilate the room and the cost of running the fan is only 13% higher than the most economical option 7. The conclusion is made for one situation (occurrence of people, room size, etc.). Given the nature of the problem of increasing concentration and reaction of the HVAC system, it can be assumed that even if the fan operating hours will vary, the ratio between the different variants will also change. The total cost per year of fan operation considered in the calculation is not very high. This situation is due to the fact that only one fan with a relatively low flow rate per room is considered. For buildings such as schools, hospitals, etc., the savings would be much more significant in the sum of all fans. References [1] DWEYER Tim: Fans for ducted ventilation systems in Icibse journal, online [https://www.cibsejournal.com/cpd/modules/2011-12/] [2] SZÉKYOVÁ, Marta. Ventilation and air conditioning. Bratislava: Jaga, 2006, 359 pp. ISBN 80807-6037-3. [3] European Standard EN 15239. Ventilation for buildings – Energy performance of buildings – Guidelines for inspection of ventilation systems [4] Nilsson, L.J. ‘Air-handling energy efficiency and design practices’, Energy & Buildings, Vol. 22 (1995), pp. 1–13 [5] Schild, P. G. ‘Ductless ventilation – Refurbishing an old listed building into modern energyefficient offices’. In Indoor Air 2008, proceedings. 2008, paper ID 646. [6] Hydeman, Taylor, Stein, Kolderup & Tong. ‘Advanced Variable Air Volume System Design Guide’, CEC Report P500-03-082-A-11, October 2003. [7] Liu, Claridge & Deng. ‘An air filter pressure loss model for fan energy calculation in air handling units’. Int. J. of Energy Research, Vol. 27 (2003), No. 6, Pp. 589–600 [8] de Almeida, A. T.; P. Angers; C. U. Brunner; M. Doppelbauer. Motors with Adjustable Speed Drives: Testing Protocol and Efficiency Standard. 2009