Evaluation and possible direct utilization of low- to medium-enthalpy geothermal resources for the sustainable development of the African continent
Full text
PROCEEDINGS OF ECOS 2023 - THE 36TH INTERNATIONAL CONFERENCE ON EFFICIENCY, COST, OPTIMIZATION, SIMULATION AND ENVIRONMENTAL IMPACT OF ENERGY SYSTEMS 25-30 JUNE, 2023, LAS PALMAS DE GRAN CANARIA, SPAIN Evaluation and possible direct utilization of lowto medium-enthalpy geothermal resources for the sustainable development of the African continent Claudio Zuffia-b, Luca Soccia, Andrea Rocchettia, Giampaolo Manfridaa and Daniele Fiaschia a Department of Industrial Engineering, University of Florence (Italy), b [email protected], CA Abstract: Lowand high-enthalpy geothermal resources exist throughout the African continent, but their utilization is still minimal. The rift valley area includes several high-enthalpy resource manifestations, but numerous mediumand low-enthalpy resources characterize the mainland. Geothermal resources offer a large energy potential suitable for several users. The main goal of this article is the assessment of the energy potential of the geothermal resources in Africa for direct use. The analysis of different types of mediumand low-enthalpy resources is carried out. The use of absorption cycles for cold production is considered here. A parametric analysis of the resource conditions, with special reference to the temperature level, allowed the estimation of the cooling power potential connected to the low to medium geothermal energy resources available in the African continent. On the other hand, possible end users of this resource are identified cold room storage and building cooling. The present study covers several aspects, from thermodynamic modelling to environmental analysis. The mathematical model allows the simulation of the cooling system and, through parametric analyses, the most suitable cycle characteristics are determined in compliance with the potential of the available geothermal resource. The Life Cycle Assessment (LCA) methodology is adopted for the sustainability analysis and the assessment of environmental compatibility of the proposed solutions. A parametric Life Cycle Inventory (LCI) is developed, modeling the components according to the required size for each use. The main outcome of the present work is that the low enthalpy Geothermal available in the African continent can offer significant energy savings and large environmental benefits, which may play a fundamental role in the sustainable development of this area. Keywords: Geothermal energy, direct use, Absorption Refrigeration System, Life Cycle Assessment 1631 https://doi.org/10.52202/069564-0148
1. Introduction Geothermal energy is acknowledged as a renewable source with a very relevant potential, and technologies to exploit it are at a rather advanced stage of development [1]. The use of this source is mainly classified into two categories: indirect, in which electricity is produced by power plants; direct, which directly exploits the geothermal heat flow for several applications, from residential to industrial heating [2]. Over the years, the installed geothermal powerplant capacity has grown extensively. In 2000, the worldwide installed capacity was 7.97 GWe producing about 49.30 GWh/y [3], while at 2020 the installed capacity had roughly doubled to 15.95 GWe producing about 95.10 GWh/y electricity [4]. The currently available technologies for electricity production are dry steam, flash steam and binary cycles, usually for medium-high enthalpy resources ranging from 120° C to 350° C. On the other hand, in a 20 years range period, the direct use of the resource has also grown extensively, from 15.14 GWt in 2000 to 107.73 GWt in 2020 installed capacity, with a growth in the produced heat from 1.9E+5 TJ/y to 1.02E+6 TJ/y at worldwide level [5]. The direct heat uses can vary widely, often involving space heating and cooling for building or industrial applications: Heat pumps, Heat Exchangers, Absorption cooling and refrigeration, greenhouses, agricultural drying, fish farming and others. The choice is highly related to the temperature level of the resource and to that required for the specific applications [6]. Generally, the direct heat use technologies belong to medium-low enthalpy resources, usually ranging between 20° C and 150° C. The African continent, and in particular the East Area where Rift valley is located, has a very high geothermal potential (over 15 GW) but the exploitation of this resource is still limited to extremely low fractions [7]. In 2020, data on the installed geothermal power in Africa amounted to 830 MWe, of which 823 MW in Kenya and 7 MW in Ethiopia. On the other hand, direct use of geothermal heat in the African continent is about 198 MWt, shared between several countries. Direct use applications are more equally distributed across the entire continent (Algeria, Burundi, Egypt, Ethiopia, Kenya, Madagascar, Malawi, Morocco, Nigeria, South Africa and Tunisia) [5]. In this context, investigating direct-use applications of geothermal heat for low to medium-enthalpy resources in the African scenario is of relevant interest. In the 40 – 150 °C heat range, the Absorption Refrigeration System (ARS) is economically and environmentally promising [8]. Several studies were conducted considering different conditions of the geothermal resource. Tugcu et al. analysed an ARS with ammonia-water mixture fed by a geothermal resource at 133°C [9]; Kairouani et al. evaluated an ARS with a mixture of ammonia and water and the geothermal resource in a range between 72°C and 75°C [10]; Velàzquez et al. have designed a singleand double-effect ARS which utilises a geothermal resource at 80°C and 163°C respectively [11]. Similarly, some paper in literature analyse the sustainability of geothermal heat for refrigeration and chilling, evaluating the coupling of the generator to different renewable sources with the Life Cycle Assessment methodology. Solano-Olivares et al. and Bukoski et al. evaluated an absorption cycle coupled with a solar system for building cooling [12], [13]. Hamedani et al. analysed the energy and environmental aspects through LCA of a biomass-fuelled heating and cooling system [14]. On the other hand, Maione et al. and Chaiyat, assessed the environmental impacts of coupling the ARS to a geothermal resource [15], [16]. In numerous regions of Africa, electricity is not easily accessible and distributed. As a result, geothermal energy plays a crucial role in the country's development. Thus, investigating systems that harness the existing heat from geothermal resources facilitates the implementation of multiple systems that would be considerably more challenging if powered by electricity. The objective of this work is modelling and evaluating the thermodynamic behaviour and the environmental impact of an ARS for different possible geothermal conditions. It is designed to cover the cooling load of a cold room (for food storage or other industrial use) or a building. The thermodynamic performance of an absorption cycle with a mixture of water and ammonia under different geothermal resource conditions have been evaluated. At the same time, the environmental impact assessment of the investigated ARS has been carried out by the means of Life Cycle Assessment (LCA), considering the construction and operation phase of the system. This work is done in the framework of the European Horizon 2020 project Long-Term Joint EU-AU Research and Innovation Partnership on Renewable Energy (LEAP-RE) [17]. 1632 https://doi.org/10.52202/069564-0148
2. Materials and methods The analysed ARS is an absorption cycle with a mixture of water and ammonia (NH3/H2O mixture) for the refrigeration of a cold room or cooling of a building. The proposed mathematical model of the ARS takes into account the chemical characterization of the mixture, the mass and energy balances. In order to realize a model suitable and easily applicable to different conditions of the African continent, several wide range variable parameters were considered. The parametric analyses focused on condensation temperature (Tcond), evaporation temperature (Tevap), mass ratio of NH3to the whole mixture (y), and finally the temperature of the geothermal resource (Tgeo). An environmental analysis was performed by the Life Cycle Assessment of the ARS, following the ISO 14040 and ISO 14044 standards [18], [19] The regulations define 4 key steps in this analysis: Goal and scope definition, Life Cycle Inventory (LCI), Life Cycle Impact Assessment (LCIA), Interpretation. In this work, the focus was on the second step, consisting in the development of a parametric LCI representing the construction phase of the absorption cycle. The goal is to provide the assessment of materials needed for construction in relation to the cooling power of the ARS, refereed to the installed kW unit. In addition, some parameters used in the thermodynamic model are set to evaluate the operation phase as well. Then, by combining the results obtained from the thermodynamic model and using them as inputs of the LCA model, it is possible to perform a comprehensive analysis of system performance and sustainability. This is done by varying the external conditions such as outdoor temperatures Tair, and target temperatures Taim. The next sections describe the thermodynamic model and the LCA model of the considered plant, outlined in Figure 1. The mathematical model of the absorption cycle was implemented in Engineering Equation Solver (EES) software [20], whereas the environmental analysis was conducted with OpenLCA software [21] and Ecoinvent 3.7 datatbase [22]. Figure 1 - Geothermal absorption cycle for refrigeration, with a mixture of water and ammonia 2.1 Energy modelling The ARS is a single-effect cycle, mainly consisting of generator, desuperheater (DSH), condenser, evaporator, absorber, and heat recovery unit (RH). The system is shifted in two lines, differently modelled according to the working fluid. At the generator outlet, from point 2 to point 6, the working fluid is pure ammonia starting as superheated vapor in 2, saturated vapor in 12, saturated liquid in 4 and saturated vapor in 6. From the generator outlet at point 3 (line 3-8) and the absorber outlet at point 9 (line 9-1) the working fluid is in the liquid state, consisting in a mixture of NH3/H2O at the concentration y. The working fluid is at a high concentration y in line 9-1 (strong solution), corresponding to the design concentration of the cycle, and at low concentration 1633 https://doi.org/10.52202/069564-0148
in line 3-8. With reference to the external conditions, two parameters mainly influence the cycle, namely the temperatures at point 4 (Tcond) and the NH3mass ration at point 9 (y), as they set the two pressure levels of the cycle: xHigh pressure corresponding to the saturation pressure of ammonia at Tcond; xLow pressure corresponding to the saturation pressure of the mixture evaluated at temperature Tcond with mass ratio y. Tcond is determined by the external conditions (1), hence the environmental air temperature, while yis set and evaluated at different level. The reason for setting the temperature T9equal to the temperature Tcond is that the absorber exchanges heat with the outside air. Tevap is evaluated from the low-pressure level as the saturation temperature at low pressure and also defines the aim temperature (Taim) achievable in the cold room or in the building (e.g. cold utility temperature) (2). Thus, these parameters uniquely set the cycle and a changing one of them leads to a variation in temperatures and pressures of the other components (Figure 2 - Temperaturepressure graph with constant water-ammonia concentration curves of the Absorption Refrigeration System), as will be seen in the Results section. ܶௗ ൌܶ οܶ ௗ (1) ܶ௩ ൌܶ οܶ ௩ (2) Figure 2 - Temperature-pressure graph with constant water-ammonia concentration curves of the Absorption Refrigeration System The whole cycle is calculated around these two fixed pressure levels. In Point 1, the water-ammonia mixture enters into the generator, which is heated by the geothermal resource. The temperature level at the generator output (point 3) is evaluated according to equation (3), where Tgeo is the temperature of the geothermal resource entering the generator. ܶଶൌܶ ଷൌܶ െοܶ (3) Thus, from point 2 the ammonia in the superheated vapour state passes through the desuperheater (DSH) and successively condenses at point 4. Downstream the isenthalpic throttling valve (4-5), the ammonia evaporates into the evaporator (5-6), providing the required refrigeration effect. At the same time, in point 3 the weak water / ammonia solution under the liquid state releases heat (thus recovered) to the NH3/H2O strong solution from the absorber. The regeneration level Rof this recuperator is defined in equation (4). ܴൌሺ݄ଷെ݄ሻሺ݄ଵെ݄ଵሻ ൘ (4) The equations governing the energy balances of the main points of the cycle are given below from (5 to 14). ܳ ൌ݉ሶ כሺ݄ଵହ െ݄ଵሻ (5) ܳ ൌ݉ሶଶכ݄ଶ݉ሶଷכ݄ଷെ݉ሶଵכ݄ଵ (6) ܳௌு ൌ݉ሶଶכሺ݄ଵଶ െ݄ଶሻ (7) 1634 https://doi.org/10.52202/069564-0148
ܳௗ ൌ݉ሶଶכሺ݄ଵଶ െ݄ସሻ (8) ܳ௩ ൌ݉ሶଶכሺ݄ସെ݄ሻ (9) ܳ௦ ൌ݉ሶଶכ݄݉ሶଷכ଼݄െ݉ሶଵכ݄ଽ (10) ݉ሶଵכሺ݄ଵെ݄ଵሻൌ݉ሶଷכሺ݄ଷെ݄ሻ (11) ܳ௦ ൌ݉ሶଶכ݄݉ሶଷכ଼݄െ݉ሶଵכ݄ଽ (12) ܹൌ݉ሶଵכሺ݄ଵ െ݄ଽሻ (13) ܥܱܲൌܳ௩ ሺܳ ܹ ሻ ൘ (14) The model relies on some fixed parameters set during the analysis, while other ones are allowed to vary. Table 1 shows all fixed and variable parameters and their values or ranges. Tcond and Tevap are evaluated to analyse their influence on the Coefficient of Performance (COP) of the whole system. The sensitivity analysis to the NH3/H2O solution concentration y is carried out to determine the most suitable ammonia concentration for the cycle in relationship to the available low-temperature level of the geothermal resources. Finally, Tgeo allows defining the performance level achievable referred to the heat input to the system. Table 1 - Range of parameters used in the parametric analysis of the system Name Parameter Unit Value /range Hot-cold side temperature difference at the condenser ΔTcond °C 10 Hot-cold side temperature difference at the evaporator ΔTevap °C 5 Hot-cold side temperature difference at the generator ΔTgeo °C 5 RH regeneration level R - 0.8 Condenser temperature T cond °C 25 – 50 Evaporator temperature Tevap °C -10 – 0 Mass fraction Ammonia/mixture y kg NH3/kg mixture 0.3 – 0.8 Geothermal mass flow rate mgeo kg/s 0.5 – 10 Temperature of resources Tgeo °C 50 – 120 2.2 LCA Modelling The surface plant for refrigeration defines the system boundaries of the analysis. Geothermal wells or the drawdown point are not considered because they are strongly site dependent. The cold room or the building are as well not considered at the analysis, as out of the focus of this work. The electricity consumption of the pumps is taken into account, and it’s impact is modelled using Kenya's electricity energy mix as a reference. The assumed functional unit is 1 kW of installed cooling power. The parametric LCI consisted in two basic steps: x Finding a reference process representative of the construction materials of the absorption cycle; x Finding enough data to establish a relationship between the installed cooling capacity and the weight of the device. 1635 https://doi.org/10.52202/069564-0148
For the first step, a literature review was conducted, and several LCIs were compared [12]–[16]. It turned out that many of them were either incomplete or referred directly to secondary processes in the database. For this reason, to consider a consistent reference, the process of the Absorption cycle provided by the Ecoinvent 3.7 database [22] was adopted as a reference model. This process was the starting point to obtain the typical composition of materials for the devices of the case study. Indeed, by neglecting the materials not closely related to the construction phase of the devices, a relative mass fraction (%) of construction materials was made per each considered unit. The second step was finding reliable catalogues of Absorber manufacturing companies. The purpose of this step is achieving information on weight and cooling power. Once obtained the necessary data, a distribution of points outlining the relationship between the weight of the devices and the nominal ARS cooling power (kW) may be traced. The World Energy Absorption Chillers Europe Ltd catalogues available online[23] were used which allowed to obtain 140 number of points. With the distribution of this data in hands, it was possible to achieve a satisfactory second-degree polynomial fitting function. The second-degree function was selected in order to limit its complexity, increasing with the polynomial degree, without entailing an appreciable reduction of the uncertainty. Figure 3 shows the point distribution and the related 2nd degree polynomial power-weight fitting function. Figure 3 - Descriptive function of installed cooling power-weight trend The conducted analysis adopts the Environmental Footprint (EF) 3.0 methodology, adapted to the Ecoinvent database. Specifically, the analysis develops on two levels: (i) Analysis of the environmental indicator Climate Change (CC) in terms of kg CO2equivalent emitted and (ii) analysis of the single score in terms of Environmental Points (Pt). The latter is achieved following normalization and weighting of all indicators evaluated by EF3.0, therefore it represents the overall environmental impact of the system. 3. Results In this section, the results coming from energy parametric analysis and LCA study are presented. In particular: xThe parametric analysis shows the sensitivity of the absorption refrigeration cycle to the ammonia concentration in the mixture, condensation temperature and geothermal resource temperature. xThe LCA study shows the contributions analysis of the environmental indicator Climate Change (CC), as well as an analysis of the most impactful categories at single score level. 3.1 Effect of ammonia concentration Figure 4 shows the temperature trend of the NH3/H2O mixture at the generator inlet T1and the evaporation temperature Tevap with respect to different y1levels. In this case, the analysis was carried out by keeping the Tgeo set at different temperature levels: a) 120°C; b) 100°C; c) 80°C; d) 60°C. The yanalysis highlights a key aspect of low-, and medium-enthalpy geothermal resources and the target temperature. The first aspect that results is that as y1increases, the temperature T1decreases and Tevap increases. Respecting the constant y = 5E-07x2+ 0.0092x + 1.5237 R² = 0.9134 0 10 20 30 40 50 60 70 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 Weight [ ton] Cooling power [kW] 1636 https://doi.org/10.52202/069564-0148
concentration curves of the ammonia-water mixture shown in Figure 2, it is denoted that as the selected curve in the Aborber-Generator stream varies, the temperature levels at the generator and evaporator also vary. This means that increasing y1allows geothermal resources to be exploited at lower temperatures. However, it must be considered that the refrigeration effect for cold room can be obtained at most for Tevap in the order of 5°C while, for the cooling of a building, Tevap must be higher than this level. As a reference, it must be considered that a satisfying refrigeration effect for a cold room can be obtained for Tevap not higher of 5°C (while, for the cooling of a building, Tevap could be higher). Taking this graph into account, it is easy to identify the NH3/H2O concentration y1which allows the required performance to be obtained with respect to the temperature of the geothermal resource. There is a grey area in the graphs, the low side of this area represents the temperature level of geothermal resource. This implies that the T1profile is not acceptable when it crosses this area and it can only assume values below that level. For low-temperature resources, the variation of y1is very limited and therefore also the terminal uses forcing only one type of application such as the cooling of buildings. Conversely, for higher temperature levels, such as a) and b), it is possible to choose both applications of cold storage and building cooling. Figure 4 - Parametric analysis of T1and Tevap as a function of y1at different level of Tgeo: a) Tgeo =120°C; b) Tgeo = 100°C; c) Tgeo = 80°C; d) Tgeo = 60°C. 3.2 Effects of condensation temperature Through the parametric analysis of Tcond, the trend of the system's COP)is investigated using a function that is also dependent on y1. In order to explore various Tcond variations, Tgeo was set to its maximum level of 120°C. Figure 5 illustrates the relationship between COP and Tcond at different levels of y1. It can be observed that at lower levels of y1, higher COP values are achieved with lower Tcond, but as y1increases, the system's performance tends to decline. However, for higher levels of y1ranging from 0.5 to 0.6, it appears that Tcond has minimal influence on COP. Since Tcond is influenced by external air temperatures, this indicates that these particular cases are minimally affected by external temperature changes, maintaining their performance almost unchanged within the typical temperature ranges of the African continent. Conversely, for cases where y1is below 0.45 to 0.35, variations in external temperatures significantly impact the system's performance, leading to a drastic drop in COP. Another consideration is that the different y1levels correspond to a specific Tevap level, which are presented in Table 2. The cases relevant to refrigeration purposes focus on y1= 0.5. Realistically, considering the outdoor temperatures commonly encountered in East Africa, the design Tcond would fall within the range of 30-40°C [24], where the COP exhibits a declining phase. Furthermore, it should be noted that a slight increase in Tevap can slightly enhance the system's performance, but it may require applications beyond refrigeration, such as building cooling. Thus, considering all the aforementioned factors, the performance of the system is highly 1637 https://doi.org/10.52202/069564-0148
dependent on its final application, as well as the external temperatures prevailing at the specific African site where the geothermal resource is located. Figure 5 - Parametric analysis of COP as a function of Tcond and Tevap 3.3 Geothermal resource The parametric analysis performed on the geothermal resource explores the trends of the COP at various y1 levels. Figure 6 depicts the overall pattern, characterized by a substantial performance increase until reaching the temperature that maximizes COP, followed by a gradual decline. The lowest point of each curve corresponds to the geothermal resource temperature at which the absorption cycle initiates operation. Considering the values presented in Table 2 and setting y1to 0.5 as the threshold for applications related to food refrigeration, it becomes evident that the minimum geothermal resource temperature is 83°C (lowest point of y1= 0.5 curve). As y1increases, corresponding to lower Tevap temperatures, the required geothermal resource temperature approaches the maximum value at a medium-low enthalpy level. In essence, lower y1 levels in the cycle necessitate higher geothermal resource temperatures. This highlights the fact that refrigeration-type applications demand minimum temperatures around 80°C, which are only available in select regions of Africa, particularly in the East Africa Rift Valley (EARV) area. Conversely, for higher y1levels, corresponding to higher Tevap temperatures, lower-temperature resources can be exploited, which are present in both the EARV and North Africa (e.g., Algeria and Morocco). Hence, it is crucial to determine the optimal ammonia concentration, y1, that maximizes COP as a function of the geothermal resource. For this reason, Table 2 provides the respective COPmax and Tgeo values for each y1 level. Figure 6 - Parametric analysis of COP as a function of Tgeo and y1 Ϭ Ϭϭ ϬϮ Ϭϯ Ϭϰ Ϭϱ Ϭϲ Ϭϳ ϲϬ ϲϱ ϳϬ ϳϱ ϴϬ ϴϱ ϵϬ ϵϱ ϭϬϬ ϭϬϱ ϭϭϬ ϭϭϱ ϭϮϬ ϭϮϱ ϭϯϬ ϭϯϱ ϭϰϬ ϭϰϱ KW dŐĞŽΣ LJϭсϬϯϱ LJϭсϬϰ LJϭсϬϰϱ LJϭсϬϱ LJϭсϬϱϱ LJϭсϬϲ LJϭсϬϲϱ 1638 https://doi.org/10.52202/069564-0148
Table 2 - Evaluation of the maximum COP with respect to the temperature of the resource and the resulting cooling power y1 0.35 0.40 0.45 0.50 0.55 0.60 0.65 Tgeo [°C] 140 137 121 106 94 83 76 Tevap [°C] -20.00 -12.56 -5.34 1.50 7.85 13.60 18.63 COP max 0.41 0.45 0.48 0. 52 0.57 0. 62 0. 65 3.4 Final application Two cases are taken as reference: a) the first has the conditions set at y1=0.5 and therefore Tevap=1.5° C for the refrigeration of a cold room for food storage purposes; b) the second has the conditions set at y1=0.6 and therefore Tevap=13.60° C for the cooling of a building. In Figure 7 an analysis is shown on the heat loads of the main components, as the geothermal resource variations. As the two graphs show, for the cooling of the building it is possible to exploit a resource at temperatures above 70°C, while for the cold room it must be above 85°C. Analysing the point at which COP is maximum for both configurations show that for case a) the cold load is 21.34 kW while for load b) it is 22.27 kW. Figure 7 - Evaluation of heat level of two different cases: On the left a) for the application of a cold room, on the right b) for the cooling of a building A preliminary dimensioning of a cold room was carried out to evaluate the output of the refrigeration and cooling system. Using equation 15 to estimate the annual cooling energy (Ecooling) in terms of kWh/y in a cold room for food storage. Where CFais the total number of hours per years of about 8000 [25], and Fris a reduction factor of about 0.5. The results obtained for the reference case is approximately 85.360 MWh. Given data from literature 73 kWh/m3per year [26] for cold room is required, so a hypothetical cold room that is met by this system is 1169 m3. At the same time, approximately 0.21kW/m2of cooling power is required for cooling a building with an internal temperature of 23°C [27]. Therefore, it can be estimated that with the analysed system a building of approximately 106 m2 can be cooled. To make a point in support of these results, consider the case of the cold room. Taking as reference the results obtained from Evans et al. 2014 [28], an estimation can be made that suggests the consumption of around 56 kWh/m3 per year for cold room. It is crucial to emphasize that the availability of electricity poses challenges in numerous African regions, which underscores the necessity to devise a system that ensures access to electricity. In this context, the utilization of the geothermal resource in Africa assumes even greater significance. ܧ ൌܳ ௩ כܥܨ כܨ (15) 1639 https://doi.org/10.52202/069564-0148