Original Article Experimental study of the unsteady vibration signature for a Sirocco fan unit Jose ´Gonza ´lez, Laura Delgado, Sandra Velarde-Sua ´rez, Jes us M Ferna ´ndez-Oro, Katia M a Argu ¨elles D ıaz, David Rodr ıguez and David Me ´ndez Abstract The small forward-curved blades known as Sirocco fan units are very common and widespread solution for air conditioning used in public transportation applications, as buses or trains. The users quietness and comfort have become a main concerns in the automotive industry. For such kind of turbomachinery flow , the patterns becomes always highly 3D and unsteady, compromising the referred comfort, and setting the focus on the working flow variables. A mathematically exact solution for that flow, which would provide any required information on pressure or forces, is out of scope at the current engineering design processes. Nevertheless, some flow features and mechanical data are needed to progress in the frame of a modern industrial environment, involving maintenance protocols with important temporal and economic constraints for different design procedures. The correctness of a given maintenance protocol relies on its feasibility to handle a set of machine working parameters or variables, including a number of them as wide as possible. Doing so, a set of not-dangerous ranges for them can be established. Such ranges are often defined promoting a series of failures similar to real ones, when the machine is in its operative lifetime. In this paper and in order to establish proper working ranges for maintenance purposes, a series of failures have been experimentally tested for a Sirocco fan unit. Initially, real data from industry have been required and a list of main failures was made, including (1) impeller or rotor unbalance, (2) impeller channel obstruction and (3) blocked inlet. The failures are studied using a purified orbit diagram (POD) technique and a symmetrized dot pattern (SDP) technique. All four working conditions are studied for at least three different flow rates and, therefore, a deeper insight into the fan working parameters and options are made feasible. In the frame of the maintenance protocol, a full set of ranges for the considered failures has been obtained. Therefore, the present paper shows a novel possibility to enhance existing maintenance protocol using two advanced frequency-based techniques. Keywords Turbomachine, fan, forward-curved blades, unsteady flows, Purified Orbit Diagram (POD), Symmetric Dot Pattern (SDP), maintenance protocol, frequency based analysis Introduction Squirrel cage or Sirocco fans are centrifugal turbomachines with forward-curved blades. Very often, they are manufactured in small sizes and commonly used in public transportation. Other practical applications cover a wide range of industrial plant usages and are also widespread on transportation applications (buses, trains and Universidad de Oviedo, Area de Meca ´nica de Fluidos, Asturias, Spain Corresponding author: Jose ´Gonza ´lez, Universidad de Oviedo, Area de Meca ´nica de Fluidos, Campus de Viesques, c/Wifredo Ricart s/n., Gij on, Asturias 33203, Spain. Email: a[email protected] Journal of Low Frequency Noise, Vibration and Active Control 0(0) 1–20 !The Author(s) 2019 DOI: 10.1177/1461348419837418 journals.sagepub.com/home/lfn Creative Commons CC BY: This article is distributed under the terms of the Creative Commons Attribution 4.0 License (http://www. creativecommons.org/licenses/by/4.0/) which permits any use, reproduction and distribution of the work without further permission provided the original work is attributed as specified on the SAGE and Open Access pages (https://us.sagepub.com/en-us/nam/open-access-at-sage).
so on). The name Sirocco fan was introduced in the classic textbook by Eck, 1 with a global overview of the existing geometries. More recently, Rouse 2 has commented on the global variables of these units, in the frame of a general fan classification. Their relative small dimensions and low cost make them competitive for residence heating systems, automotive units or other industrial applications. Their working parameters include a high specific speed and a large width-to-diameter ratio (b/D 2 ), while the flow deceleration imposed by the blade passages precludes the separation inception, as explained by Kind. 3 Other important features, as the short chord and the large number of blades, were previously pointed out by Kind and Tobin 4 where a particular and detailed study of the geometry and flow features is given. Globally speaking, this kind of unit becomes an economic solution when dealing with a small unit for a relatively high flow rate delivery. Due to the before mentioned interest and current applications, the number of classical studies on forwardcurved centrifugal fans is quite exhaustive, going from the initial experimental search for secondary flow patterns in Cau et al. 5 to more advanced and complementary experimental and numerical works. 6 Other and more recent studies, for instance, Kim and Seo, 7 Engin 8 and Velarde-Sua ´rez et al., 9,10 have proposed a series of geometrical modifications or rearrangements to improve some given design parameters as, for instance, the performance enhancement or the noise reduction, among others. Particularly, Engin 8 studied the flow in the tip region of centrifugal fans, using a numerical approach. In the same frame, and as a starting point for the work presented here, the study by Ballesteros-Tajadura et al. 11 has shown a numerical solution for the pressure fluctuations in the volute of a centrifugal fan unit. The importance of a proper definition of a maintenance protocol for any kind of mechanical machine is deeply referred in the bibliography and several works are available, like the one by Jardine et al. 12 with a wide review on the topic. The particular features for rotating machines and different approaches are explained in Chen et al., 13 Lu et a. 14 and Cui and Craighead 15 Regarding the diagnosis of failures in fans, a number of very important frequencies are numbered in Chen et al. 13 as theoretical values. Failure characteristics or diagnostic indexes cannot be defined quantitatively, but other failure characteristics are clearly observed, as explained in Shi et al. 16 On the other hand, the Fast Fourier Transform (FFT) has been established as the standard method to obtain the corresponding spectra revealing its composition in the frequency domain, see examples in Lu et al. 14 and Shi et al. 16 Nevertheless, some other methods are available in the literature, see for instance Shibata et al. 17 and Bianchi et al., 18 and may also be considered as relevant tools. Combining both methodologies (numerical and experimental), a study about the flow in a forward-curved centrifugal fan was proposed by Lin and Huang. 6 Focusing on the thermal performance of small units used for cooling purposes in personal computers, they provide a quite ambitious parametric study of the aerodynamic and sound properties of different geometries, both experimentally and numerically. Considering the previously mentioned studies and many other important contributions which might be found in the bibliography, the interest on the topic is clear. The present work takes into account the researchers concern about the definition of a maintenance protocol using an experimental approach. Both POD and SDP techniques are used to complement previous efforts of the research group, according to different previous publications. 19–22 It can be considered in the frame of previous works by the same working team, see for instance, Velarde-Sua ´rez et al., 9 Ballesteros-Tajadura et al. 11,19 Gonza ´lez et al. 20,21 and Delgado et al. 22 Regarding the SDP method, interesting recent contributions are those by Bianchi et al. 18 and Wu et al., 23 for slightly different machines and Shibata et al. 17 for a generic rotating machine. This study describes a sort of predictive maintenance that allows to realize the fan operating diagnosis by means of detecting aerodynamic instability. There are several methods that analyze vibration or pressure signals by means of the amplitude variation in the time or in the frequency domain, although sometimes the signals of the incipient failure are not detected during the application of these methods and additional time delays would be required to identify them. Thus, these methods are difficult to apply for the continuous monitoring of the performance of the machines, see Bianchi et al. 18 and Meng et al., 24 also complemented for fans by the more recent works by Zhang et al. 25 or Xu et al. 26,27 Nevertheless, the SDP technique shows visually the amplitude and frequency variations of the pressure or vibration signals. Furthermore, the SDP diagram could be obtained with the data acquired during only one rotor revolution, so it is fast enough for its application to a realtime monitoring. Geometrical arrangements The squirrel cage fan studied in this article is a double impeller unit, arranged as shown in Figure 1. The two impellers are placed at both sides of the electrical motor and supported by the two sides of the shaft in cantilever. 2Journal of Low Frequency Noise, Vibration and Active Control 0(0)
The shaft produces also the rotation of both impellers in a forward direction with respect to the blade curvature. Covering the whole unit, there is a volute or external casing, providing two rectangular outlet sections. In such arrangement, each impeller is not producing a symmetric flow due to the presence of an obstructed inlet at the motor side of each impeller. In other words, there is a free inlet, at each impeller side opposite to the placement of the motor, but also an obstructed inlet, next to the motor side. Additionally, each impeller is built with two staggered parts, which are linked together by a central plate, as can be observed in Figures 1 and 2. The staggering of these two parts means that, for each impeller, they are mounted producing a shift of the 23 blades, so that the mechanical resonances are minimized (see Figure 2). Figure 3 shows the piece connecting the fan outlet with the test benchmark. The main working parameters can be found in previous works, see Ballesteros-Tajadura et al. 20 or Gonza ´lez et al. 21 Experimental set-up and measurements To consider a given fault diagnosis protocol, different measurements must be taken for different operation conditions producing, in such way, different standard faults to the fan under study. The obtained measurements will provide a possible comparison of the observed changes in the fans performance with the baseline, or operation without any fault. In the present study, apart from the baseline operation, two different faults have been considered for the experimental study: one blade-to-blade channel obstruction and an unbalanced impeller operation. The facility, properly instrumented to carry out the designed measurements, was arranged as shown in Figure 4. The fan is placed at one end of the pipe and in the other end, a regulation cone is installed. Here, the studied variable is the vibrating state of the fan. For its definition, two B&K-4384 fast response piezoelectric accelerometers are available. They are connected to a charge amplifier, B&K-2635, especially suitable for acceleration measurements. The sensitivity of the sensors is 10 pC/g. The cut frequency for the accelerometers is 10 kHz, although the maximum valid frequency was found to be 3 kHz due to the particular arrangement for the tests. The measurements chain is completed with the acquisition unit Harmonie, connected to the PC. The whole set-up is schematically represented in Figure 4. Tests repeatability was carried out for several configurations and Figure 1. Simplified schematic of the tested fan. Figure 2. Each of the two impellers. Gonza ´lez et al. 3
different flow rates, showing maximum variations of the characteristic peaks below 3%. To account for the fan working point, three different flow rates were studied: nominal flow rate and two off-design working points (one at 0.7 and other at 1.3, respectively, and relative to the nominal one). An example of the recorded data is shown in Figure 5. The unsteady acceleration is recorded in a time basis for a series of impeller rotations, in order to get enough resolution. After application of the FFT procedure, a frequency domain signal is obtained, typically as shown in Figure 6. It corresponds to a low flow rate and for the baseline operation. As can be read in Chen et al., 13 the expected peaks and their meaning are always quite clear for rotating machinery. From most relevant peaks, a set of failure conditions might be analyzed. Nevertheless, the focus of the present paper is to find out the most relevant frequencies in order to achieve or define a good diagnosis for the studied failures. With this purpose in mind, a full study of the relevant peaks is mandatory and the result will be analyzed in detail in what follows. As a starting point, real data from industry have been required and a list of main failures was made, including (1) impeller or rotor unbalance, (2) impeller channel obstruction and (3) blocked inlet. The considered faults are the first two ones, as the blocked inlet changes the performance operation of the fan and a comparison with the baseline operation becomes unrealistic in terms of flow rate delivery. As observed in Figure 6, the purified spectrum depends only in the values of a few, but stronger or more relevant frequencies. If there is a change in value or phase for any other frequency, the spectrum will remain constant. Firstly, the nominal flow rate is considered and then, two others were analyzed, a low and high one Figure 3. Test bench, ready for the fan. Figure 4. Tested fan and measurements chain. 4Journal of Low Frequency Noise, Vibration and Active Control 0(0)
respectively, in order to cover the possible fan working range. The three operation conditions considered at the experimental campaign were: the baseline operation, obstructed channel and unbalanced rotor operation. The impeller arrangement for these failures is shown in Figure 7. A detail of the obstructed channel failure is shown in Figure 7 (left picture). For the unbalance of the rotor, small metal pieces of 1.6 g (including the fixing material) were fixed up to one of the fan blades, as can be observed in Figure 7 (right picture). POD and SDP analysis The purified orbit diagram (POD) technique consists of a spectral analysis technique that may be applied to different measurements when those evolve over time. In the particular application studied in the present paper, a POD technique is applied to the horizontal and vertical signals recorded from the two sensors used (see Figure 3 for the global setting of the sensors at the fan casing). An example of the time signal recorded is shown in Figure 5 for nominal flow rate and baseline operation. These kinds of signals were recorded for the three different operations and for three representative flow rates. The implemented procedure, following the global frame depicted in Chen et al., 13 works as follows: (i) Measure of the time signal for the horizontal and vertical components of the acceleration. The acceleration is recorded as a function of time, following the experimental routine and apparatus previously described. Figure 5. Example of a recorded time evolution. Figure 6. Signal after FFT analysis. Figure 7. Impeller modifications for the two failure operations considered. Gonza ´lez et al. 5
(ii) Apply a standard FFT to get the frequency decomposition of the signals. The information is transformed into a set of data (f k ,u(k)), that is, into the frequency domain, and splitting the energy components for the different frequencies. (iii) Search for the predominant frequencies with their relative values and obtain the (so called) modified spectrum of the signal (S). This new value is a simplification of the real spectrum considering only N frequencies of interest or relatively more intense than the others. Therefore, S is a filtered spectrum at the stronger measured frequencies. In our particular application, the following are found to be the most relevant frequencies (not all apply to all operations but no others related to electrical or others were found to be important), as shown in Table 1. (iv) Apply the POD technique to get the purified spectrum. The following equations are considered to obtain the horizontal and vertical component of the orbit diagram, according to the equation Xx ðÞ j;POD ¼X N k¼1 SxðkÞcos 2pjfkþ/hðkÞðÞ Xy ðÞ j;POD ¼X N k¼1 SyðkÞsin 2pjfkþ/vðkÞðÞ 8 > > > > > < > > > > > : (1) Alternatively, the SDP technique is an algorithm which provides a visual correlation that allows to recognize the peculiarities of any signal and to distinguish each other. In this study, this technique is used to link each vibration signal with its operating condition respectively, so that, visually, it allows to determine if a machine is operating properly and, if it were not the case, it is even possible to diagnose the failure it has. By means of this technique, a radial and an angular component is assigned to each point of the periodic wave. The expressions used to do the polar transformation R(i) from polar wave to SDP are the following set of equations Figure 8. Typical time signal with relevant points for SDP technique. Table 1. Most relevant frequencies observed in the study. Frequency Number Meaning f 1 1 Rotating or main frequency f 2 2 Second harmonic of the main frequency f 3 3 Third harmonic of the main frequency f 4 4 Fourth harmonic of the main frequency f 8 8 Eighth harmonic of the main frequency f 16 16 Sixteenth harmonic of the main frequency 6Journal of Low Frequency Noise, Vibration and Active Control 0(0)
Ri ðÞ¼rðiÞrmin rmax rmin Hþi ðÞ¼H0þrðiþLÞrmin rmax rmin n Hi ðÞ¼H0rðiþLÞrmin rmax rmin n 8 > > > > > > > < > > > > > > > : (2) where i is the position of the considered dot (from a total number of points, M ¼t/Dt, being t the sampling time and the Dt¼1/f of data acquisition); L is the time lag coefficient, r(i) is the value of the vibration data of the considered dot; r max and r min , respectively, represent the maximum value and the minimum of the original periodic wave (Figure 8); H 0 is the rotation of initial angle of any reference line; nis the gain of the plotting and H þ and H – are the angles in the polar diagram. Therefore, to make the transformation of the input waveform into a SDP plot, it is necessary to determine first the r max and r min values of the sample and then apply the previous expressions. Regarding the sine type periodical waves, it was noticed that the lobe curvature depends on the variety of frequencies of the sampling and the fuzziness on the sampling amplitude which increases the thickness of the SDP fingerprint. SDP is a method with the purpose of representing, in a visual and easy-to-understand way, changes in the amplitude and frequency of periodic signals. The parameters that are necessary to set in order to obtain a good SDP pattern are the time lag coefficient L and the angular gain n. Figure 9 shows the plot variation depending on the L and nvalues selected. For this study, values of L ¼6 and n¼1.2were chosen as they provided optimal SDP fingerprints. The sampling frequency and the acquisition time were 10 kHz and 0.2048 s, respectively. These values correspond to a given number of rotor revolutions during the sampling time. Note that due to variations in the driven frequency of the electrical motor as a function of the flow rate (see Gonza ´lez et al. 21 ), the number of the rotor revolutions for the same acquisition time depends on the fan flow. In the case of high flow rate, the speed of the rotor was 4125 r/min, so the sampling time lasted 14 revolutions of the rotor, whereas for the medium flow Figure 9. Parameters sensitivity for the SDP analysis. Gonza ´lez et al. 7
Figure 10. SDP patterns for different impeller revolutions at nominal flow rate. Figure 11. POD vector summation of the different frequencies for the nominal flow rate, left, and high flow rate, right. 8Journal of Low Frequency Noise, Vibration and Active Control 0(0)
rate lasted 15 revolutions and finally for the low flow rate 16 revolutions were recorded (see Figure 10). Also, in Figure 10, the different SDP fingerprints obtained for nominal flow rates at different sampling times showed that differences between the SDP fingerprints are practically marginal. Thus, an acceptable analysis could be realized using a sampling time of 53 ms, that is 4 rotor revolutions only. From the kind of spectrum as the one shown in Figure 6, the POD technique is then applied to the nine studied data sets. After doing the peak selection, Figure 11 shows the composition of peaks and the resulting diagram for the nominal flow rate and the baseline operation. As the whole diagram is a summation of vectors, the result is graphically obtained as explained for the first point. Repeating this for a full rotation of the blades (a 360turning of the impeller), the result is the plotted diagram or, in other words, the outer or envelope curve on Figure 11. In this particular graph, the result is the summation of the three most relevant frequencies: f 1 ,f 2 and f 4 . Also, the strongest signal or the most relevant one is the rotation frequency (f 1 ). Then, it can be appreciated the fourth harmonic as second stronger one and, finally, the second harmonic, with relative less importance. Other harmonics influence at a lower level and, therefore, are not considered, obtaining in such way the POD of the signal. The vector summation of the three components is the result shown in Figure 11 (only the first point of the data set is remarked) and it resembles the POD graph of the nominal flow rate at the baseline operation of the fan. It shows a maximum vibration resultant for an angle near 45, which indicates the almost equal contribution of the vertical and horizontal components in the vibration of the machine. For each rotation of the impeller, the composition of the x and y components, for a given flow rate, completes one of the elliptical-shape figures (similar to the one in Figure 11). The procedure is then repeated for the low and high flow rates. The result for the high flow rate and baseline operation is shown in Figure 11. The predominant frequencies are, for this working point, the rotating frequency and the four basic harmonics. Again, the vector summation is showed for the first point. The POD graph for this flow rate becomes more vertical than the one obtained in Figure 11. In this flow rate and operating at the baseline condition, the vertical component of the force is more important than the horizontal one. Note that the scale for the two diagrams in Figure 11 is not the same and, therefore considering this scale change, the relative importance of each POD is re-scaled and compared in Figure 12. The comparison shows how the vibration at a high flow rate is less important, but with an order of magnitude very similar to the nominal flow rate. The highest vibrating levels are found at the low flow rate, with maximum vibration almost twice as the maximum for the other two analyzed flow rates. Results and discussion Initially, the POD results are considered, then the SDP is analyzed, and finally a global remark is done on a crosscomparison basis of the two methods. Figure 12. POD for the baseline operation and the three studied flow rates. Gonza ´lez et al. 9
Another possibility of interpretation would be to eliminate from the SDP fingerprint the set of dots that encircle the regions without dots. Figure 18 shows the SDP diagram obtained by the application of this procedure. The lobes of the obstructed channel SDP obtained in this way have a shorter length than for the normal operating and unbalanced rotor SDP as Figure 19 shows. This is due to the fact that, for the obstructed channel operating state, the predominant waves are of low frequency and their amplitude is larger than in the other cases. The machine operating condition will be determined by the acceleration value and by the orbit shape that shows the direction of the predominant acceleration. As regards SDP fingerprints, the dot absence inside the lobes indicates the presence of low frequency vibration components (considering low frequencies as being those lower than the rotating frequency in each operating condition: high flow 70 Hz, medium flow 75 Hz and low flow 80 Hz) so that, a greater dot amount inside the lobes will indicate the predominance of high frequencies. Figure 20. POD and SDP comparison for the low flow rate. 16 Journal of Low Frequency Noise, Vibration and Active Control 0(0)
On the other hand, it is necessary to consider the thickness of the lobes. This is associated with the vibration wave amplitude value of the sample, therefore the greater it is, the greater the lobe thickness will be. Keeping these criteria in mind, a relationship could be observed between SDP and DOP diagrams. Figures 20 and 21 show the comparison for the two kinds of diagrams. Regarding the normal operating SDP diagram obtained by the vertical sensor, it denotes that the vibration wave amplitude values are low but even so they are higher than the ones acquired by the horizontal sensor and this is shown in the DOP diagram with an orbit that indicates a vertical acceleration value higher than the horizontal acceleration value (Figure 20). The low flow unbalanced rotor SDP diagram obtained by the vertical sensor data (Figure 20), provides wider lobes with a big region without dots in its center,which indicates that the predominant waves are of low frequency and of a considerable amplitude. This is reflected by the high acceleration value of the DOP diagram. To explain Figure 21. POD and SDP results for the high flow rate. Gonza ´lez et al. 17
the horizontal acceleration value, it is necessary to study the horizontal sensor SDP diagram. The lobe thickness is similar to the normal operating lobes and have some regions without dots in its inside because the higher amplitude waves are equally distributed in the frequency spectrum, so the acceleration value of the DOP diagram is a little higher than the one for the normal operation. From the obstructed channel SDP diagrams, it could be observed that the vertical and horizontal accelerations have a very similar value, as shown in the DOP diagram, since the inside of the horizontal sensor SDP lobes are the negative of the values of the vertical sensor. For the other off-design condition (Figure 21), the results of both techniques also become complementary. Vertical sensor data again provide wider lobes with a big region without dots in its center, indicating that the predominant waves are of low frequency and of considerable amplitude. This is also reflected by the high acceleration value of the DOP diagram. For the horizontal sensor, lobe thickness is also of the same range as for the normal operation and higher regions without dots appear in the diagrams. Conclusions The dynamic effects of the flow in a centrifugal fan have been studied by the experimental recording of vibration signals, following two perpendicular directions, the horizontal and vertical. Considering the experiments, two well-established fault diagnosis protocols, namely the POD and SDP techniques were considered in order to describe the fan operation and characterize it. The main conclusions of the experiments and POD analysis indicate that the highest vibration to be found is 2.5 times the gravitational acceleration, and it happens for the unbalanced of the impeller fault. The lower vibration is always for the baseline operation at any flow rate, with a maximum of 0.3 times the gravitational acceleration. The obstructed channel configuration shows a quite different behavior in comparison with the baseline and the unbalance of the impeller. A minimum of vibrations is found for the baseline operation and relatively high flow rates. At off-design flow rates, the unbalanced impeller fault results in higher accelerations, while for the nominal flow operation, both studied faults produce equivalent acceleration values. The SDP technique allows for incipient fan failure detection so, when the SDP fingerprint obtained from the vibration analysis is different from the normal operating SDP, it will be possible to identify if it will produce a mechanical failure or not. The regions without dots inside the SDP fingerprint lobes denote the presence of low frequency vibrational components and the lobes thickness increases with the vibration wave amplitude, that is, with the acceleration value. The normal operating SDP lobes do not present regions without dots and they are narrower than the lobes for the other operating conditions due to the low value of the accelerations that appear in this case. Overall, the SDP technique is simpler than the POD technique. In addition, the SDP diagrams obtained by the horizontal and vertical sensors allow an approximation of the POD orbit form by observing the lobes shape, because the greater their thickness, the greater the acceleration value. Nevertheless, to know the horizontal and vertical acceleration values, it would be necessary to apply the POD technique. A lower data treatment is required for the SDP method and the search of the characteristic frequencies is not necessary, this technique is a fully visual one. Considering the global overview, the study preludes a maintenance method for small centrifugal fans. The main fault diagnosis study performed gives already an idea of the main working range parameters and the possible fault detection procedures. Finally, it can be stated that the studied techniques do extend the state of the art for the considered machine. Acknowledgements The authors acknowledge the constant cooperation and permission for the publication of the article, provided by Hispacold Internacional, S.A. Mainly, the help of Juan Bernal-Cant on must be recognized. Declaration of conflicting interests The author(s) declared no potential conflicts of interest with respect to the research, authorship, and/or publication of this article. 18 Journal of Low Frequency Noise, Vibration and Active Control 0(0)
Funding The author(s) disclosed receipt of the following financial support for the research, authorship, and/or publication of this article: The financial support from the “Ministerio de Ciencia e Innovaci on” (under Projects numbers TRA2007-62708, DPI2011-25419, ENE2017-89965-P and “Tecnolog ıas ecol ogicas para el transporte Urbano, ecoTRANS” (CDTI) is also gratefully acknowledged. The financial support of the Instituto Universitario de Tecnolog ıa Industrial (IUTA), through projects SV-17-GIJON-1-07 and SV-18-GIJON-1-04 has also helped in the final stages of the present study. References 1. Eck B. Fans. 1st English ed. Oxford, UK: Pergamon Press, 1973. 2. Rouse S. (coordinator), Fans reference guide (2001), Ontario Power Generation. 3. Kind RJ. Prediction of flow behavior and performance of squirrel-cage centrifugal fans operating at medium and high flow rates. Trans J Fluids Eng 1997; 119: 639–646. 4. Kind RJ and Tobin MG. Flow in a centrifugal fan of the squirrel cage type. J Turbomach 1990; 112: 84–90. 5. Cau G, Mandas N, Manfrida N, et al. Measurements of primary and secondary flows in an industrial forward-curved centrifugal fan. J Fluids Eng 1987; 109: 353–358. 6. Lin S and Huang C. An integrated experimental and numerical study of forward–curved centrifugal fan. Exp Therm Fluid Sci 2002; 26: 421–434. 7. Kim K and Seo S. Shape optimization of forward-curved-blade centrifugal fan with Navier-Stokes analysis. J Fluids Eng 2004; 126: 735–742. 8. Engin T. Study of tip clearance effects in centrifugal fans with unshrouded impellers using computational fluid dynamics. Proc IMechE J Power and Energy Part A 2006; 220: 596–610. 9. Velarde-Suarez S, Ballasteros-Tajadura R, Santolaria-Morros C, et al. Unsteady flow pattern characteristics downstream of a forward curved blades centrifugal fan. J Fluids Eng 2001; 123: 265–270. 10. Velarde-Sua ´rez S, Ballesteros-Tajadura R, Santolaria-Morros C, et al. Reduction of the aerodynamic tonal noise of a forward-curved centrifugal fan by modification of the volute tongue geometry. Proc ASME Fluids Eng Summer Meet 2005; 2: 89–94. 11. Ballesteros-Tajadura R, Velarde-Sua ´rez S, Hurtado-Cruz JP, et al. Numerical calculation of pressure fluctuations in the volute of a centrifugal fan. J Fluids Eng 2006; 128: 359–369. 12. Jardine AKS, Lin D and Banjevic D. A review on machinery diagnostics and prognostics implementing condition-based maintenance. J Mech Systems Signal Process 2006; 20: 1483–1510. 13. Chen YD, Du R and Qu LS. Fault features of large rotating machinery and diagnosis using sensor fusion. J Sound Vib 1995; 188: 227–242. 14. Lu Z, Wang C, Qiu N, et al. Experimental study on the unsteady performance of the multistage centrifugal pump. J Brazil Soc Mech Sci Eng 2018; 40: 264. 15. Cui D and Craighead IA. A new approach to assess the quality of small high speed centrifugal fans using noise measurement. Int J Rotat Mach 1999; 5: 147–153. 16. Shi DF, Qu LS and Gindy NN. General interpolated Fast Fourier Transform: a new tool for diagnosing large rotating machinery. J Vib Acoust 2005; 127: 351–361. 17. Shibata K, Takahashi A and Shirai T. Fault diagnosis of rotating machinery through visualization of sound signals. Mech Syst Signal Process 2000; 14: 229–241. 18. Bianchi S, Corsini A, Sheard AG, et al. A critical review of stall control techniques in industrial fans. Hindawi ISRN Mech Eng 2013; 52619. 19. Ballesteros-Tajadura R, Guerras FI, Velarde-Sua ´rez S, et al. Numerical model for the unsteady flow features of a squirrel cage fan. Proc ASME Fluids Engineering Summer Meet, FEDSM 2009-78479, Vail, Colorado, USA, 2: 173–183. 20. Gonza ´lez J, Ballesteros-Tajadura R, Velarde-Sua ´rez S, et al. Inspection and diagnostic criteria for fans installed in air conditioning systems of public transport vehicles. In: ASME mechanical engineering congress and exposition, Vancouver, Canada, 2010. 21. Gonza ´lez J, Delgado L, Ferna ´ndez Oro JM, et al. Purified orbit diagram and numerical study for a failure analysis of a Sirocco fan. Adv Mech Eng 2017; 9: 1–17. 22. Delgado L, Gonza ´lez J, Ferna ´ndez Oro JM, et al. Fault diagnosis technique for a squirrel cage fan using vibration analysis signals. Proc ASME Fluids Engineering Summer Meet, Chicago, IL, USA, FEDSM2014-21232; 1: 1–8. 23. Wu J and Chuang C. Fault diagnosis of internal combustion engines using visual dot patterns of acoustic and vibration signals. NDT& E Int 2005; 38: 605–614. 24. Meng Y, Lu L and Yan J. Shaft orbit feature based rotator early unbalance fault identification. Proc CIRP 2016; 56: 512–515. 25. Zhang H, Wang MZ, Li H, et al. Shaft orbit analysis based on Labview for fault diagnosis of rotating machinery. In: 11th international conference on computer science & education (ICCSE-2016), Nagoya, Japan, ThP 8.2, pp.972–975. Gonza ´lez et al. 19
26. Xu X, Liu H, Zhu H, et al. Fan fault diagnosis based on symmetrized dot patter analysis and image matching. J Sound Vib 2016; 374: 297–311. 27. Xu X, Liu H, Wang S, et al. Real-time stall detection of centrifugal fan based on the analysis of symmetrized dot pattern and wavelet packet transform. J Vibro Eng 2017; 19: 1823–1832. Appendix Notation a acceleration (m/s 2 ) b impeller width (m) D 2 impeller exit diameter (m) FFT fast Fourier transform f frequency (Hz) g gravity constant (m/s 2 ) h, v horizontal and vertical sensors i, j, k indexes for a given frequency () L time shift for the SDP technique (s) M total number of points () N number of considered frequencies () POD purified orbit diagram, one of the techniques used in the paper R polar value of a given signal S amplitude of the spectrum, once FFT is applied (m/s 2 ) SDP symmetrized Dot Pattern, one of the techniques being used t, Dt time and sampling time (s) X value of a given signal (m/s 2 ) x,y coordinate system (m) /(k) phase of a signal at a given frequency (rad) rvalue of the vibration signal for the SDP analysis ngain of the values plotted in the SDP analysis Hphase values for the SDP analysis (rad) 20 Journal of Low Frequency Noise, Vibration and Active Control 0(0)