Influence of the Improvement in Thermal Expectation Levels with Adaptive Setpoint Temperatures on Energy Consumption

David Bienvenido-Huertas; Daniel Sánchez-García; Carlos Rubio-Bellido; Jesús A. Pulido-Arcas

Abstract

A sustainable use of active heating, ventilation, and air conditioning (HVAC) systems is crucial for minimum energy consumption. Currently, research studies are increasingly applying adaptive setpoint temperatures, thus reducing considerably the energy consumption without influencing comfort levels excessively. Most of them, however, are focused on the limit values of adaptive comfort standards without considering the tolerance in users’ adaptation capacity. This research study analyzed various tolerance ranges in the recent adaptive thermal comfort model from EN 16798-1:2019 used in setpoint temperatures. The study focused on the south of Europe, considering 47 cities in Spain, 18 cities in Portugal, 13 cities in Greece, and 20 cities in Italy. In addition, such cities were analyzed in three climate scenarios: present time, 2050, and 2100. The results showed that values prefixed by EN 16798-1:2019 for new buildings (tolerance of 0.00 °C) produced significant savings with respect to the static model and that each progressive improvement in users’ thermal expectations in 0.25 °C increased the energy consumption between 6.57 and 9.31% in all scenarios analyzed. Even applying a thermal tolerance of 1.50 °C, energy savings are currently produced with respect to the static model. This tendency increases in future scenarios until a thermal tolerance of 1.75 °C. The results of this paper provide greater knowledge about the possible energy increase that the improvement in users’ expectations would produce

Full text

applied sciences Article Influence of the Improvement in Thermal Expectation Levels with Adaptive Setpoint Temperatures on Energy Consumption David Bienvenido-Huertas 1,* , Daniel Sánchez-García1, Carlos Rubio-Bellido 1and Jesús A. Pulido-Arcas 2 1Department of Building Construction II, University of Seville, 41012 Seville, Spain; [email protected] (D.S.-G.); [email protected] (C.R.-B.) 2Center for Research and Development of Higher Education, Graduate School of Arts and Sciences, College of Arts and Sciences, The University of Tokyo, Tokyo 113-8654, Japan; [email protected] *Correspondence: [email protected] Received: 6 July 2020; Accepted: 29 July 2020; Published: 30 July 2020   Abstract: A sustainable use of active heating, ventilation, and air conditioning (HVAC) systems is crucial for minimum energy consumption. Currently, research studies are increasingly applying adaptive setpoint temperatures, thus reducing considerably the energy consumption without influencing comfort levels excessively. Most of them, however, are focused on the limit values of adaptive comfort standards without considering the tolerance in users’ adaptation capacity. This research study analyzed various tolerance ranges in the recent adaptive thermal comfort model from EN 16798-1:2019 used in setpoint temperatures. The study focused on the south of Europe, considering 47 cities in Spain, 18 cities in Portugal, 13 cities in Greece, and 20 cities in Italy. In addition, such cities were analyzed in three climate scenarios: present time, 2050, and 2100. The results showed that values prefixed by EN 16798-1:2019 for new buildings (tolerance of 0.00 ◦ C) produced significant savings with respect to the static model and that each progressive improvement in users’ thermal expectations in 0.25 ◦ C increased the energy consumption between 6.57 and 9.31% in all scenarios analyzed. Even applying a thermal tolerance of 1.50 ◦ C, energy savings are currently produced with respect to the static model. This tendency increases in future scenarios until a thermal tolerance of 1.75 ◦ C. The results of this paper provide greater knowledge about the possible energy increase that the improvement in users’ expectations would produce. Keywords: adaptive comfort; setpoint temperature; energy consumption; climate change; energy efficiency 1. Introduction By 2050, it is estimated that the European building stock will have reduced greenhouse gas emissions by 90% when compared to 1990 [ 1 ]. If this reduction percentage is achieved, it will strongly affect climate change control due to the activity of the building stock [ 2 ]. In addition, other social and health aspects, such as energy poverty [ 3 – 5 ] or mortality because of inappropriate thermal conditions [ 6 , 7 ], could be reduced. The improvement in building energy performance is therefore crucial. For this purpose, attention should be paid on the use of heating, ventilation, and air conditioning (HVAC) systems as they are the main energy consumption source in buildings [ 8 , 9 ]. The combination of energy conservation measures with smart designs will improve the performance of the building stock. However, the main challenges for a more sustainable use of energy in buildings are not just focused on obtaining buildings with better systems [ 10 , 11 ], a better envelope [ 12 – 14 ], and an energy self-production [15–17], but also on the use of buildings [18,19]. Appl. Sci. 2020,10, 5282; doi:10.3390/app10155282 www.mdpi.com/journal/applsci Appl. Sci. 2020,10, 5282 2 of 22 The influence of users on the behavior of HVAC systems is due to the main goal of such systems: to maintain satisfactory thermal conditions inside the dwelling. One of the possibilities to reduce this energy consumption is by modifying setpoint temperatures [ 20 ]. The nudge of the HVAC system setpoint temperatures can strongly impact the energy performance of the building [ 21 ], mainly due to its influence on the energy demand required for the HVAC system [ 22 ]. In this regard, Lakeridou et al. [ 23 ] analyzed the effect of increasing the cooling setpoint temperature by 2 ◦ C in a field study conducted in an administrative building in 2010. A total of 129 participants were surveyed, and the results showed that the rise in the setpoint temperature did not affect their thermal comfort. Hoyt et al. [ 24 ] studied the energy saving obtained by varying the setpoint temperatures of HVAC systems in office buildings. Significant savings were obtained in the energy consumption, with variations of 1 ◦ C in heating and of 3 ◦ C in cooling. A similar study was carried out by Spyropoulos and Balaras [ 25 ]. In this study, the authors studied several Greek bank branches. The use of setpoint temperatures of 20 ◦ C for heating and of 26 ◦ C for cooling achieved energy savings of up to 45%. Fernandez et al. [ 26 ] analyzed the effect of increasing the range of the thermostat by 1.1 ◦ C in heating and cooling, as well as other improvement measures in the HVAC systems of office buildings. Energy savings oscillated between 12 and 20%. Parry et al. [ 27 ] studied the possibilities of reducing the energy consumption of a Swiss office building. Increasing the cooling setpoint temperature up to 4 ◦ C reduced the annual building energy consumption by a third. Additionally, Saidur [ 28 ] analyzed that the increase in the air conditioning setpoint temperature from 22 to 26 ◦ C can save by 24% the energy consumption of office buildings in Malaysia. Likewise, Yamtraipat et al. [ 29 ] evaluated the effect of increasing the air conditioning setpoint temperature by 26 ◦ C in 13 office buildings in Thailand. The results showed a total saving of 804.60 GWh/year. Finally, Moon and Han [ 30 ] analyzed the effect of gradually increasing the setpoint temperatures in residential buildings in Detroit and Miami. The results reflected that, depending on the type of climate, the modification of the setpoint temperatures influenced heating in cold climates and cooling in hot climates. Most of these research studies considered that HVAC systems are used with static setpoint temperatures. The use of this type of setpoint temperatures has discrepancies with the adaptability of users to real buildings [ 31 – 33 ]. There is solid evidence, however, that users perceive comfort according to the external thermal variations [ 34 ]. In this regard, users of residential buildings can adopt adaptive strategies limiting the energy consumption of HVAC systems [ 35 , 36 ]. Thus, the use of such new adaptive comfort models to adjust setpoint temperatures (i.e., adaptive setpoint temperatures) of buildings is an opportunity to guarantee important energy savings without influencing users’ thermal comfort. The possible energy savings by implementing such models have been investigated by several research studies. In a first study, Van der Linden et al. [ 37 ] analyzed the energy saving achieved by applying the thermal comfort model from kennisinstituut voor de installatiesector (ISSO) 74 [ 38 ]. The use of the lower limit of such standard achieved an energy saving of 74%. Later, Yun et al. [ 39 ] carried out another study with this approach. In their work, the authors analyzed the application of the adaptive comfort model to the operational conditions of air conditioning systems in an office building. The results showed the possibility of using the adaptive thermal comfort model with 87% of users satisfied. However, recent studies have focused on the energy savings which can be achieved in residential buildings. S á nchez-Guevara S á nchez et al. [ 40 ] studied the variation of setpoint temperatures in three residential buildings located in various cities in Spain. Setpoint temperatures monthly varied by using the adaptive thermal comfort model from American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) 55-2017 [ 41 ]. The energy consumption of the case studies analyzed was reduced between 20 and 80%. Likewise, in a recent study, S á nchez-Garc í a et al. [ 42 ] studied the application of adaptive setpoint temperatures in a residential building. The analysis was conducted in the same cities on which the study by S á nchez-Guevara S á nchez et al. [ 40 ] was based. The energy consumption was saved between 10 and 46% according to the type of climate in which the building was located. In another study, Wang et al. [ 43 ] evaluated different approaches to use the thermostat, including the ASHRAE adaptive comfort model. This analysis was performed Appl. Sci. 2020,10, 5282 3 of 22 on residential buildings in five United States cities (San Francisco, New York City, Phoenix, Miami, and Fairbanks). The results showed savings of up to 54% with the adaptive model power consumption. Finally, Bienvenido-Huertas et al. [ 44 ] analyzed the influence of the alpha value used to calculate the prevailing mean outdoor temperature with adaptive setpoint temperatures. The results showed deviations of up to 0.47 and 1.30% in heating and cooling energy consumption, respectively. Nevertheless, the various research studies related to the application of adaptive setpoint temperatures present several knowledge gaps. The first knowledge gap is related to the tolerance of applying such limit values. Under actual application conditions, users are likely to have limitations to reach the limit values of the adaptive comfort standards. In such standards, the increase in limit values means a decrease in percentage of acceptability of the category. It is also fundamental to consider the influence of users’ habits. In this regard, it is worth stressing that the adaptation capacity of the occupants’ thermal comfort usually has asymmetric trajectories [ 45 ]. Users more used to the use of HVAC systems will have therefore more difficulties to increase the limit values of the operative temperature than those not using such systems [ 45 ]. For this reason, this study analyzed various tolerance ranges in the adaptive thermal comfort model used in setpoint temperatures. The study was focused on new buildings as this type of constructions is where users could have a greater demand in thermal comfort limits. To do this, the amplitude of comfort limits was reduced by intervals of 0.25 ◦ C, and consequently, the amplitude of the comfort zone was narrowed to a total of 0.5 ◦ C in each interval by increasing the tolerance variable. Furthermore, other three important gaps of the previous studies have been tackled in this research. The first gap is related to the adaptive thermal comfort model used because most research studies were based on EN 15251:2007 [ 46 ]. However, this standard has been recently modified by EN 16798-1:2019 [ 47 ]. As a result, new research studies using the new standard will give updating knowledge about the effectiveness of adaptive setpoint temperatures. Secondly, the comparison of results from the application of adaptive setpoint temperatures with respect to static effective setpoint temperatures will lead to greater knowledge about the saving degree. Thirdly, most research studies were conducted in certain cities by using adaptive setpoint temperatures. For this reason, this research analyzed many cities from various countries: 47 cities in Spain, 18 cities in Portugal, 13 cities in Greece, and 20 cities in Italy. Among countries of the European Union, these four countries were selected due to their great climate vulnerability to climate change. These cities correspond to the capitals of the regions of each country. Additionally, the analysis was conducted in the current climate scenario, as well as in unfavorable climate change scenarios for 2050 and 2100. This paper is divided as follows: on the one hand, theoretical bases of adaptive comfort models related to the various levels of users’ tolerance, how climate simulations were performed, and the modelling of dwelling used in the study are explained in the methodology; on the other hand, results are discussed as follows: the effect of the increase in tolerance in heating and cooling consumption in the current scenario is first discussed for the various regions considered, and the same process is then conducted for 2050 and 2100. Finally, the most relevant conclusions are drawn. 2. Methodology 2.1. Thermal Comfort Model: Adaptive Setpoint Temperatures and Tolerances The European adaptive thermal comfort model currently in force is EN 16798-1:2019 [ 47 ]. This standard led to the update of EN 15251:2007 [ 46 ]. EN 16798-1:2019 establishes three different categories in which the internal operative temperature should oscillate according to the type of building and to occupants’ expectations (e.g., category I should be used in spaces for people with special requirements, such as old people or ills, category II should be used in new buildings, and category III in existing buildings). Such categories indicate the values in which the internal operative temperature should oscillate through upper and lower limits. Equations (1) and (2) indicate the limit values of category II (i.e., Appl. Sci. 2020,10, 5282 4 of 22 new buildings) [ 47 ], which is the aim of this research. Such limits are established through linear correlations whose independent variable is an external average temperature known as the running mean outdoor temperature ( Trm ). Trm is obtained by the weighted sum of daily mean external temperatures from the previous days (see Equation (3)) [ 47 ]. It is important to note that Trm will be useful not only to obtain the limits of the internal operative temperature, but to determine whether the adaptive comfort model from EN 16798-1:2019 could be applied. In this sense, EN 16798-1:2019 establishes that the adaptive comfort model could be applied if Trm is between 10 and 30 ◦C. Upper limit (Category II)=0.33·Trm +21.8 [◦C] (10 ≤Trm ≤30)(1) Lower limit (Category II)=0.33·Trm +14.8 [◦C] (10 ≤Trm ≤30)(2) Trm =Text,day−1+0.8Text,day−2+0.6Text,day−3+0.5Text,day−4+0.4Text,day−5+0.3Text,day−6 +0.2Text,day−7/3.8 [◦C](3) As discussed above, many research studies have analyzed the use of the upper and lower limits of the adaptive model as the setpoint temperatures of HVAC systems. The use of the limit values of the adaptive model could lead to significantly save the energy consumption. However, its use implies a higher level of users’ adaptability, so it is necessary to analyze the effect of better users’ thermal expectations with respect to the limit values of the adaptive thermal comfort model. For this purpose, the limit values related to category II were used. Heating and cooling limits were reduced in intervals of 0.25 ◦ C, narrowing the comfort zone to a total of 0.5 ◦ C in each interval. Figure 1 graphically represents the limits of the thermal comfort models used in this study. The numeric value indicates the designation of the adaptive thermal comfort model which coincides with the reduction in degrees with respect to the limit values of category II. Concerning the values assigned to setpoint temperatures when the adaptive thermal comfort model is not applied, the criterion used in other similar research studies was used [ 42 , 48 ]: to horizontally extend the comfort limits. Furthermore, a static model was used as a reference model. The static model was designed by using the static setpoint temperatures set in the standard of adaptive comfort for HVAC systems: between 20 and 25 ◦ C for heating periods, and between 23 and 26 ◦ C for cooling periods. Table 1summarizes the correlations and limit values used in each model. Appl. Sci. 2020, 10, x FOR PEER REVIEW 4 of 23 correlations whose independent variable is an external average temperature known as the running mean outdoor temperature (𝑇𝑟𝑚 ). 𝑇𝑟𝑚 is obtained by the weighted sum of daily mean external temperatures from the previous days (see Equation (3)) [47]. It is important to note that 𝑇𝑟𝑚 will be useful not only to obtain the limits of the internal operative temperature, but to determine whether the adaptive comfort model from EN 16798-1:2019 could be applied. In this sense, EN 16798-1:2019 establishes that the adaptive comfort model could be applied if 𝑇𝑟𝑚 is between 10 and 30 °C. 𝑈𝑝𝑝𝑒𝑟 𝑙𝑖𝑚𝑖𝑡 (𝐶𝑎𝑡𝑒𝑔𝑜𝑟𝑦 𝐼𝐼) = 0.33 ∙ 𝑇𝑟𝑚 +21.8 [°𝐶] (10 ≤ 𝑇𝑟𝑚 ≤ 30) (1) 𝐿𝑜𝑤𝑒𝑟 𝑙𝑖𝑚𝑖𝑡 (𝐶𝑎𝑡𝑒𝑔𝑜𝑟𝑦 𝐼𝐼) = 0.33 ∙ 𝑇𝑟𝑚 +14.8 [°𝐶] (10 ≤ 𝑇𝑟𝑚 ≤ 30) (2) 𝑇𝑟𝑚 = (𝑇𝑒𝑥𝑡,𝑑𝑎𝑦−1 + 0.8𝑇𝑒𝑥𝑡,𝑑𝑎𝑦−2 + 0.6𝑇𝑒𝑥𝑡,𝑑𝑎𝑦−3 + 0.5𝑇𝑒𝑥𝑡,𝑑𝑎𝑦−4 + 0.4𝑇𝑒𝑥𝑡,𝑑𝑎𝑦−5 + 0.3𝑇𝑒𝑥𝑡,𝑑𝑎𝑦−6 + 0.2𝑇𝑒𝑥𝑡,𝑑𝑎𝑦−7)/3.8 [°𝐶] (3) As discussed above, many research studies have analyzed the use of the upper and lower limits of the adaptive model as the setpoint temperatures of HVAC systems. The use of the limit values of the adaptive model could lead to significantly save the energy consumption. However, its use implies a higher level of users’ adaptability, so it is necessary to analyze the effect of better users’ thermal expectations with respect to the limit values of the adaptive thermal comfort model. For this purpose, the limit values related to category II were used. Heating and cooling limits were reduced in intervals of 0.25 °C, narrowing the comfort zone to a total of 0.5 °C in each interval. Figure 1 graphically represents the limits of the thermal comfort models used in this study. The numeric value indicates the designation of the adaptive thermal comfort model which coincides with the reduction in degrees with respect to the limit values of category II. Concerning the values assigned to setpoint temperatures when the adaptive thermal comfort model is not applied, the criterion used in other similar research studies was used [42,48]: to horizontally extend the comfort limits. Furthermore, a static model was used as a reference model. The static model was designed by using the static setpoint temperatures set in the standard of adaptive comfort for HVAC systems: between 20 and 25 °C for heating periods, and between 23 and 26 °C for cooling periods. Table 1 summarizes the correlations and limit values used in each model. Figure 1. Limit values of the adaptive thermal comfort model for new buildings from EN 16798-1:2019 and the analyzed tolerances. Dashed lines show the tolerances considered. Appl. Sci. 2020,10, 5282 5 of 22 Table 1. The setpoint temperature adapted to each model analyzed. Model Tolerance Setpoint Temperature (◦C) Trm <10 10 ≤Trm ≤30 Trm >30 Lower Limit Upper Limit Lower Limit Upper Limit Lower Limit Upper Limit Adaptive 0.00 18.1 25.1 0.33·Trm +14.8 0.33·Trm +21.8 24.7 31.7 0.25 18.35 24.85 0.33·Trm +15.05 0.33·Trm +21.55 24.95 31.45 0.50 18.6 24.6 0.33·Trm +15.3 0.33·Trm +21.3 25.2 31.2 0.75 18.85 24.35 0.33·Trm +15.55 0.33·Trm +21.05 25.45 30.95 1.00 19.1 24.1 0.33·Trm +15.8 0.33·Trm +20.8 25.7 30.7 1.25 19.35 23.85 0.33·Trm +16.05 0.33·Trm +20.55 25.95 30.45 1.50 19.6 23.6 0.33·Trm +16.3 0.33·Trm +20.3 26.2 30.2 1.75 19.85 23.35 0.33·Trm +16.55 0.33·Trm +20.05 26.45 29.95 2.00 20.1 23.1 0.33·Trm +16.8 0.33·Trm +19.8 26.7 29.7 2.25 20.35 22.85 0.33·Trm +17.05 0.33·Trm +19.55 26.95 29.45 2.50 20.6 22.6 0.33·Trm +17.3 0.33·Trm +19.3 27.2 29.2 2.75 20.85 22.35 0.33·Trm +17.55 0.33·Trm +19.05 27.45 28.95 3.00 21.1 22.1 0.33·Trm +17.8 0.33·Trm +18.8 27.7 28.7 Static -20 a25 a20 a25 a20 a25 a 23 b26 b23 b26 b23 b26 b aHeating period, bCooling period. 2.2. Cities Analyzed In a recent study, the applicability of adaptive thermal comfort models throughout the planet was evaluated [ 49 ]. The results showed a relationship between latitude and the application of the adaptive thermal comfort models. In this sense, latitudes near the equator have an application of more than 90% of the days of the year, while latitudes near the geographic poles have an application lower than 10% [ 49 ]. This aspect is due to the values that external temperatures usually have at each latitude. Therefore, the variation of the external temperature is among the fundamental aspects in the use of adaptive thermal comfort models. However, there are regions far from the equator in which an adequate application of adaptive thermal comfort models was detected, such as the Mediterranean region [49]. As this research aimed at having greater knowledge about the application of this type of setpoint temperature, the main cities of countries in southern Europe with the greatest surface were analyzed (Figure 2). The criterion chosen to select the cities was that they were the capitals of the regions of each country. These cities usually have a greater population and a higher building energy consumption [ 50 , 51 ]. Therefore, the study of these cities would allow to analyze the energy-saving potential that can be achieved under the climatic conditions where the buildings with the highest energy consumption are located. As a result, 47 cities in Spain, 18 cities in Portugal, 13 cities in Greece, and 20 cities in Italy were selected (see Table 2). As for Greece, it is worth stressing that the regional division was based on the 13 regions set in the Kallikratis Plan [52], which was enforced in 2011. Appl. Sci. 2020,10, 5282 6 of 22 Appl. Sci. 2020, 10, x FOR PEER REVIEW 6 of 23 Figure 2. Countries considered. Table 2. Cities considered from each country. Country Capital City Greece Athens, Ermoupoli, Ioannina, Irakleio, Kerkyra, Komotini, Kozani, Lamia, Larisa, Mytilini, Patra, Thessaloniki, and Tripoli Italy Ancona, Aosta, Bari, Bologna, Cagliari, Campobasso, Catanzaro, Florence, Genoa, L’Aquila, Milan, Naples, Palermo, Perugia, Potenza, Rome, Trento, Trieste, Turin, and Venice Portugal Aveiro, Beja, Braga, Bragança, Castelo Branco, Coimbra, Evora, Faro, Guarda, Leiria, Lisboa, Portalegre, Porto, Santarem, Setubal, Viana Castelo, Vila Real, and Viseu Spain Albacete, Alicante, Almeria, Avila, Badajoz, Barcelona, Bilbao, Burgos, Caceres, Cadiz, Castellon, Ciudad Real, Cordoba, Cuenca, Gerona, Granada, Guadalajara, Huelva, Huesca, Jaen, La Coruña, Leon, Lerida, Logroño, Lugo, Madrid, Malaga, Murcia, Orense, Oviedo, Palencia, Pamplona, Pontevedra, Salamanca, San Sebastian, Santander, Segovia, Seville, Soria, Tarragona, Teruel, Toledo, Valencia, Valladolid, Vitoria, Zamora, and Zaragoza As mentioned in Section 1, the results of this research were obtained through an exhaustive simulation process. Simulations were performed with EnergyPlus. To do this, obtaining the EnergyPlus weather (EPW) files of each city was required. Such EPW files were used for simulations and for the determination of the limit values of adaptive models (see Figure 3). This is done through the hourly temperature data available in each EPW. With these data, it is possible to determine the daily average temperature data in each file, and by applying Equations (1)–(3), the upper and lower limits of thermal comfort are determined. EPW files were obtained through METEONORM [53]. METEONORM is a software made up of 8325 weather stations which generates climate schedule values in any Earth’s location through spatial interpolations. The radiation period considered for generating the EPW files was 1991–2010, and the temperature period was 2000–2009. This research was also aimed at analyzing the influence of tolerances on the adaptive setpoint temperatures in future climate change scenarios. The EPW files of each cities were therefore obtained in the years 2050 and 2100 through METEONORM. The former was selected because it is the year established by the European Union to reduce by 90% the greenhouse gas emissions generated by the building sector, and the latter was selected to analyze the behavior of the adaptive strategies at the end of the 21st century. Scenario A2 from the Intergovernmental Panel on Climate Change was chosen as it is one of the most unfavorable scenarios [54]. Such scenario considers a very heterogeneous world and is characterized by a constant increase in population and with economic developments focused on each region [54]. In this scenario, a rise in temperatures between 2 and 5.4 °C is forecast at the end of the 21st century with respect to the values at the end of the 20th century. Despite the fact that the representative concentration pathways are the last scenarios published, the uncertainty regarding the future evolution of climate throughout the 21st century does not allow us Figure 2. Countries considered. Table 2. Cities considered from each country. Country Capital City Greece Athens, Ermoupoli, Ioannina, Irakleio, Kerkyra, Komotini, Kozani, Lamia, Larisa, Mytilini, Patra, Thessaloniki, and Tripoli Italy Ancona, Aosta, Bari, Bologna, Cagliari, Campobasso, Catanzaro, Florence, Genoa, L’Aquila, Milan, Naples, Palermo, Perugia, Potenza, Rome, Trento, Trieste, Turin, and Venice Portugal Aveiro, Beja, Braga, Bragança, Castelo Branco, Coimbra, Evora, Faro, Guarda, Leiria, Lisboa, Portalegre, Porto, Santarem, Setubal, Viana Castelo, Vila Real, and Viseu Spain Albacete, Alicante, Almeria, Avila, Badajoz, Barcelona, Bilbao, Burgos, Caceres, Cadiz, Castellon, Ciudad Real, Cordoba, Cuenca, Gerona, Granada, Guadalajara, Huelva, Huesca, Jaen, La Coruña, Leon, Lerida, Logroño, Lugo, Madrid, Malaga, Murcia, Orense, Oviedo, Palencia, Pamplona, Pontevedra, Salamanca, San Sebastian, Santander, Segovia, Seville, Soria, Tarragona, Teruel, Toledo, Valencia, Valladolid, Vitoria, Zamora, and Zaragoza As mentioned in Section 1, the results of this research were obtained through an exhaustive simulation process. Simulations were performed with EnergyPlus. To do this, obtaining the EnergyPlus weather (EPW) files of each city was required. Such EPW files were used for simulations and for the determination of the limit values of adaptive models (see Figure 3). This is done through the hourly temperature data available in each EPW. With these data, it is possible to determine the daily average temperature data in each file, and by applying Equations (1)–(3), the upper and lower limits of thermal comfort are determined. EPW files were obtained through METEONORM [ 53 ]. METEONORM is a software made up of 8325 weather stations which generates climate schedule values in any Earth’s location through spatial interpolations. The radiation period considered for generating the EPW files was 1991–2010, and the temperature period was 2000–2009. This research was also aimed at analyzing the influence of tolerances on the adaptive setpoint temperatures in future climate change scenarios. The EPW files of each cities were therefore obtained in the years 2050 and 2100 through METEONORM. The former was selected because it is the year established by the European Union to reduce by 90% the greenhouse gas emissions generated by the building sector, and the latter was selected to analyze the behavior of the adaptive strategies at the end of the 21st century. Scenario A2 from the Intergovernmental Panel on Climate Change was chosen as it is one of the most unfavorable scenarios [ 54 ]. Such scenario considers a very heterogeneous world and is characterized by a constant increase in population and with economic developments focused on each region [ 54 ]. In this scenario, a rise in temperatures between 2 and 5.4 ◦ C is forecast at the end of the 21st century with respect to the values at the end of the 20th century. Despite the fact that the representative concentration pathways are the last scenarios published, the uncertainty regarding the future evolution of climate throughout the 21st century does not allow us to determine the scenario that will finally take place [ 55 ]. For this reason, the analysis of the building energy performance in the future should be contextualized with the climate change scenario used [ 56 ]. This study used a scenario Appl. Sci. 2020,10, 5282 7 of 22 A2 as it is widely applied [57–64] and is among the scenarios with the highest incidence of climate in the Special Report on Emissions Scenarios [54]. Appl. Sci. 2020, 10, x FOR PEER REVIEW 7 of 23 to determine the scenario that will finally take place [55]. For this reason, the analysis of the building energy performance in the future should be contextualized with the climate change scenario used [56]. This study used a scenario A2 as it is widely applied [57–64] and is among the scenarios with the highest incidence of climate in the Special Report on Emissions Scenarios [54]. Figure 3. Examples of the internal operative temperature obtained in the current scenario in the city of Seville with adaptive models with tolerance of 0.00, 1.50, and 3.00 °C, and the static model. The heating setpoint temperature is represented in red line, and the cooling setpoint temperature in blue line. 2.3. Case Study For simulations, a virtual prototype building was designed (see Figure 4). This prototype case study is an ideal residential building designed according to the minimum energy demand criteria established for new buildings in the countries analyzed [65,66]. It is a building with a rectangular floor plan of dimensions of 12 × 10 m and it has two dwellings per floor. The internal space of each dwelling is divided into a bedroom, a bathroom, a kitchen, a living room, and a corridor. The use of a virtual prototype of case studies to establish considerations and operational hypotheses has been used in various studies: (i) Grazieschi et al. [66] used a virtual prototype of a two-story building to analyze optimal solutions in the life cycle of an autonomous building; (ii) Rossi and Rocco [67] designed a virtual test-room to analyze the influence of the periodic thermal transmittance and the internal areal heat capacity on the energy demand of the interior space; (iii) Rodrigues et al. [68] and Fernandes et al. [69] designed a wide variety of virtual prototypes of residential buildings using the Evolutionary Program for the Space Allocation Problem algorithm to assess the influence of thermal properties on energy performance; (iv) Jiru [70] and Abediniangerabi et al. [71] analyzed different virtual prototypes of buildings included in the ASHRAE Standard 90-2010 to evaluate energy conservation measures; (v) Kim et al. [72] analyzed the performance of the variable refrigerant flow and the rooftop variable air volume systems in a virtual prototype of an office building; (vi) O’Neill and Niu [73] used a virtual prototype of a single-family home to assess the effect of occupancy on energy performance; (vii) Shishegar and Boubekri [74] used a four-story virtual office building to Figure 3. Examples of the internal operative temperature obtained in the current scenario in the city of Seville with adaptive models with tolerance of 0.00, 1.50, and 3.00 ◦ C, and the static model. The heating setpoint temperature is represented in red line, and the cooling setpoint temperature in blue line. 2.3. Case Study For simulations, a virtual prototype building was designed (see Figure 4). This prototype case study is an ideal residential building designed according to the minimum energy demand criteria established for new buildings in the countries analyzed [ 65 , 66 ]. It is a building with a rectangular floor plan of dimensions of 12 × 10 m and it has two dwellings per floor. The internal space of each dwelling is divided into a bedroom, a bathroom, a kitchen, a living room, and a corridor. The use of a virtual prototype of case studies to establish considerations and operational hypotheses has been used in various studies: (i) Grazieschi et al. [ 66 ] used a virtual prototype of a two-story building to analyze optimal solutions in the life cycle of an autonomous building; (ii) Rossi and Rocco [ 67 ] designed a virtual test-room to analyze the influence of the periodic thermal transmittance and the internal areal heat capacity on the energy demand of the interior space; (iii) Rodrigues et al. [ 68 ] and Fernandes et al. [ 69 ] designed a wide variety of virtual prototypes of residential buildings using the Evolutionary Program for the Space Allocation Problem algorithm to assess the influence of thermal properties on energy performance; (iv) Jiru [ 70 ] and Abediniangerabi et al. [ 71 ] analyzed different virtual prototypes of buildings included in the ASHRAE Standard 90-2010 to evaluate energy conservation measures; (v) Kim et al. [ 72 ] analyzed the performance of the variable refrigerant flow and the rooftop variable air volume systems in a virtual prototype of an office building; (vi) O’Neill and Niu [ 73 ] used a virtual prototype of a single-family home to assess the effect of occupancy on energy performance; (vii) Shishegar and Boubekri [ 74 ] used a four-story virtual office building to evaluate the installation of daylight controllers; (viii) Sardoueinasab et al. [ 75 ] used a virtual prototype of the Pacific Northwest National Laboratory office building to analyze air leaks in the parallel fan-powered Appl. Sci. 2020,10, 5282 8 of 22 terminal units; (ix) Ciancio et al. [ 57 ] used a virtual prototype of a residential building to assess its energy demand with climate change in different cities in Europe. Appl. Sci. 2020, 10, x FOR PEER REVIEW 8 of 23 evaluate the installation of daylight controllers; (viii) Sardoueinasab et al. [75] used a virtual prototype of the Pacific Northwest National Laboratory office building to analyze air leaks in the parallel fan-powered terminal units; (ix) Ciancio et al. [57] used a virtual prototype of a residential building to assess its energy demand with climate change in different cities in Europe. Figure 4. Scheme of the model of the case study designed. Regarding the virtual prototype used in the research, it is important to highlight that, to reduce the elements through which heat transfers take place, the case study corresponded to an intermediate floor, so that heat losses or gains produced through the roof were reduced. Given the aim of this study (analyzing the effect of the variation of setpoint temperatures on the energy consumption), both thermal properties and the load profile were the same in all locations, so there were no other factors varying the energy consumption: variations in the energy consumption were caused by setpoint temperatures. The thermal properties of the vertical elements are specified in Table 3. Regarding windows, a design with a thermal transmittance of 4.2 W/(m2K) and a constant solar heat gain coefficient (SHGC) of 0.6 were used. Table 3. Thermal properties of external and internal walls. Element Layer Thickness (m) Thermal Conductivity (W/(mK)) Thermal Capacity (J/(kgK)) Density (kg/m3) External wall 1.Perforated brick 0.115 0.350 1000 780 2.Cement mortar 0.015 1.000 1000 1700 3.EPS insulation 0.020 0.032 1450 50 4.Hollow brick 0.070 0.320 1000 770 5.Gypsum plaster 0.015 0.570 1000 1000 Internal wall 1. Plasterboard 0.025 0.250 1000 900 2. Air gap 0.100 - - - 3. Plasterboard 0.025 0.250 1000 900 Regarding the load profile, a similar profile than that used in previous research studies was used [42,48]. Figure 5 presents the hourly percentage contribution of each load. The profile considers that the occupancy of the case study varies depending on the day: from Monday to Friday, the occupancy varies from 25 to 100%, whereas Saturdays and Sundays the case study has an occupancy of 100%. The load of lighting devices and equipment has the same usage profile, which varies depending on the time of the day. Values of 100% for the various loads are as follows: the latent load is 1.36 W/m2, the sensitive load is 2.15 W/m2, and the load for both equipment and lighting devices is 4.40 W/m2. It Figure 4. Scheme of the model of the case study designed. Regarding the virtual prototype used in the research, it is important to highlight that, to reduce the elements through which heat transfers take place, the case study corresponded to an intermediate floor, so that heat losses or gains produced through the roof were reduced. Given the aim of this study (analyzing the effect of the variation of setpoint temperatures on the energy consumption), both thermal properties and the load profile were the same in all locations, so there were no other factors varying the energy consumption: variations in the energy consumption were caused by setpoint temperatures. The thermal properties of the vertical elements are specified in Table 3. Regarding windows, a design with a thermal transmittance of 4.2 W/(m 2 K) and a constant solar heat gain coefficient (SHGC) of 0.6 were used. Table 3. Thermal properties of external and internal walls. Element Layer Thickness (m) Thermal Conductivity (W/(mK)) Thermal Capacity (J/(kgK)) Density (kg/m3) External wall 1. Perforated brick 0.115 0.350 1000 780 2. Cement mortar 0.015 1.000 1000 1700 3. EPS insulation 0.020 0.032 1450 50 4. Hollow brick 0.070 0.320 1000 770 5. Gypsum plaster 0.015 0.570 1000 1000 Internal wall 1. Plasterboard 0.025 0.250 1000 900 2. Air gap 0.100 - - - 3. Plasterboard 0.025 0.250 1000 900 Regarding the load profile, a similar profile than that used in previous research studies was used [ 42 , 48 ]. Figure 5presents the hourly percentage contribution of each load. The profile considers that the occupancy of the case study varies depending on the day: from Monday to Friday, the occupancy varies from 25 to 100%, whereas Saturdays and Sundays the case study has an occupancy of 100%. The load of lighting devices and equipment has the same usage profile, which varies depending on the time of the day. Values of 100% for the various loads are as follows: the latent load is 1.36 W/m 2 , the sensitive load is 2.15 W/m 2 , and the load for both equipment and lighting devices is 4.40 W/m 2 . It is worth stressing that the case study was designed with a variable refrigerant flow (VRF) system with a Appl. Sci. 2020,10, 5282 9 of 22 coefficient of performance (COP) of 3.10 and an energy efficiency ratio (EER) of 3.00. Regarding the thermal comfort models and the setpoint temperatures, Table 1indicated the values associated with the upper and lower limits of each adaptive model. Likewise, Table 1indicated the setpoint temperatures considered for the static thermal comfort approach. These values were configured in the simulations carried out of the case study in EnergyPlus. Figure 6summarizes the simulation process carried out in the research. Appl. Sci. 2020, 10, x FOR PEER REVIEW 9 of 23 is worth stressing that the case study was designed with a variable refrigerant flow (VRF) system with a coefficient of performance (COP) of 3.10 and an energy efficiency ratio (EER) of 3.00. Regarding the thermal comfort models and the setpoint temperatures, Table 1 indicated the values associated with the upper and lower limits of each adaptive model. Likewise, Table 1 indicated the setpoint temperatures considered for the static thermal comfort approach. These values were configured in the simulations carried out of the case study in EnergyPlus. Figure 6 summarizes the simulation process carried out in the research. Figure 5. Hourly distribution of loads. Figure 6. Flow chart of the simulation process. 3. Results and Discussion Firstly, simulations were performed. A total of 14 simulations were performed in each city and three climate scenarios were analyzed (current day, 2050, and 20,100), so results are based on 4116 different simulations. Then, such data were independently analyzed according to the climate scenario. Section 3.1 shows and discusses the results obtained in the current scenario, and Section 3.2 discusses the comparative analysis among the different countries. Finally, Section 3.3 deals with the results obtained in 2050 and 2100. 3.1. Effect of the Increase in Tolerance in the Current Scenario By analyzing the results of the current scenario, it was found that the level of users’ thermal expectations progressively increased in the building energy consumption. Figure 7 shows that the Figure 5. Hourly distribution of loads. Appl. Sci. 2020, 10, x FOR PEER REVIEW 9 of 23 is worth stressing that the case study was designed with a variable refrigerant flow (VRF) system with a coefficient of performance (COP) of 3.10 and an energy efficiency ratio (EER) of 3.00. Regarding the thermal comfort models and the setpoint temperatures, Table 1 indicated the values associated with the upper and lower limits of each adaptive model. Likewise, Table 1 indicated the setpoint temperatures considered for the static thermal comfort approach. These values were configured in the simulations carried out of the case study in EnergyPlus. Figure 6 summarizes the simulation process carried out in the research. Figure 5. Hourly distribution of loads. Figure 6. Flow chart of the simulation process. 3. Results and Discussion Firstly, simulations were performed. A total of 14 simulations were performed in each city and three climate scenarios were analyzed (current day, 2050, and 20,100), so results are based on 4116 different simulations. Then, such data were independently analyzed according to the climate scenario. Section 3.1 shows and discusses the results obtained in the current scenario, and Section 3.2 discusses the comparative analysis among the different countries. Finally, Section 3.3 deals with the results obtained in 2050 and 2100. 3.1. Effect of the Increase in Tolerance in the Current Scenario By analyzing the results of the current scenario, it was found that the level of users’ thermal expectations progressively increased in the building energy consumption. Figure 7 shows that the Figure 6. Flow chart of the simulation process. 3. Results and Discussion Firstly, simulations were performed. A total of 14 simulations were performed in each city and three climate scenarios were analyzed (current day, 2050, and 20,100), so results are based on 4116 different simulations. Then, such data were independently analyzed according to the climate scenario. Section 3.1 shows and discusses the results obtained in the current scenario, and Section 3.2 discusses the comparative analysis among the different countries. Finally, Section 3.3 deals with the results obtained in 2050 and 2100. 3.1. Effect of the Increase in Tolerance in the Current Scenario By analyzing the results of the current scenario, it was found that the level of users’ thermal expectations progressively increased in the building energy consumption. Figure 7shows that the distribution of the annual results of energy consumption in all the cities analyzed progressively increased both consumptions (heating and cooling). Furthermore, such increase led to an energy Appl. Sci. 2020,10, 5282 16 of 22 is achieved with low tolerances, the increase in tolerance means a progressive loss of the saving in heating degrees, even increasing heating degrees with respect to the static model. Appl. Sci. 2020, 10, x FOR PEER REVIEW 16 of 23 presents a progressive increase throughout the 21st century due to the rise in external temperatures. This tendency, however, is not reflected in the total energy consumption due to the saving in heating degrees. While a high saving in heating degrees is achieved with low tolerances, the increase in tolerance means a progressive loss of the saving in heating degrees, even increasing heating degrees with respect to the static model. Figure 11. Box-plots with the energy consumption distribution obtained in all cities with each configuration of static setpoint temperatures in the three scenarios (current day, 2050, and 2100). Figure 12. Box-plots of the saving in heating and cooling degrees between adaptive models and the static model in the three scenarios (current day, 2050, and 2100). The rise in external temperatures throughout the 21st century implies that the maximum tolerance interval from which the energy consumption is worse than that of the static model increases. Table 9 represents the average increase or decrease percentages of the energy consumption. The maximum thermal tolerance interval, from which a decrease in total energy consumption is obtained, went from 1.50 °C in the current scenario to 1.75 °C in 2050 and 2100 because of the progressive importance of the cooling consumption and of its potential of energy saving with respect to the static setpoint temperature of 26 °C. Moreover, the rise in thermal tolerance in 0.25 °C in 2050 and in 2100 presents similar tendencies of percentage increase to those obtained in the current scenario, with an Figure 11. Box-plots with the energy consumption distribution obtained in all cities with each configuration of static setpoint temperatures in the three scenarios (current day, 2050, and 2100). Appl. Sci. 2020, 10, x FOR PEER REVIEW 16 of 23 presents a progressive increase throughout the 21st century due to the rise in external temperatures. This tendency, however, is not reflected in the total energy consumption due to the saving in heating degrees. While a high saving in heating degrees is achieved with low tolerances, the increase in tolerance means a progressive loss of the saving in heating degrees, even increasing heating degrees with respect to the static model. Figure 11. Box-plots with the energy consumption distribution obtained in all cities with each configuration of static setpoint temperatures in the three scenarios (current day, 2050, and 2100). Figure 12. Box-plots of the saving in heating and cooling degrees between adaptive models and the static model in the three scenarios (current day, 2050, and 2100). The rise in external temperatures throughout the 21st century implies that the maximum tolerance interval from which the energy consumption is worse than that of the static model increases. Table 9 represents the average increase or decrease percentages of the energy consumption. The maximum thermal tolerance interval, from which a decrease in total energy consumption is obtained, went from 1.50 °C in the current scenario to 1.75 °C in 2050 and 2100 because of the progressive importance of the cooling consumption and of its potential of energy saving with respect to the static setpoint temperature of 26 °C. Moreover, the rise in thermal tolerance in 0.25 °C in 2050 and in 2100 presents similar tendencies of percentage increase to those obtained in the current scenario, with an Figure 12. Box-plots of the saving in heating and cooling degrees between adaptive models and the static model in the three scenarios (current day, 2050, and 2100). The rise in external temperatures throughout the 21st century implies that the maximum tolerance interval from which the energy consumption is worse than that of the static model increases. Table 9 represents the average increase or decrease percentages of the energy consumption. The maximum thermal tolerance interval, from which a decrease in total energy consumption is obtained, went from 1.50 ◦ C in the current scenario to 1.75 ◦ C in 2050 and 2100 because of the progressive importance of the cooling consumption and of its potential of energy saving with respect to the static setpoint temperature of 26 ◦ C. Moreover, the rise in thermal tolerance in 0.25 ◦ C in 2050 and in 2100 presents similar tendencies of percentage increase to those obtained in the current scenario, with an increase between 6.83 and 9.31% in 2050 and between 6.79 and 8.73% in 2100. As a result, the improvement in users’ thermal expectations always presents a similar increase tendency of the building energy Appl. Sci. 2020,10, 5282 17 of 22 consumption, although the energy-saving percentages with respect to a static behavior could vary with respect to the future climate change scenarios. Table 9. Percentage deviation between the energy consumption of the adaptive model and the consumption of the static model in the three scenarios. Positive values correspond to a decrease in energy consumption, and negative values correspond to an increase. Tolerance Percentage Deviation (%) Current 2050 2100 Cooling Heating Total Cooling Heating Total Cooling Heating Total 0.00 68.90 26.48 38.74 62.37 26.91 41.93 53.60 26.80 43.59 0.25 64.32 21.34 33.67 57.68 21.00 36.92 49.43 19.46 38.90 0.50 58.73 16.01 28.77 52.68 14.90 31.76 45.14 11.63 34.08 0.75 52.68 10.42 23.34 47.14 8.52 26.24 40.41 3.28 28.89 1.00 45.89 4.58 17.65 41.14 1.93 20.45 35.37 −5.58 23.44 1.25 38.34 −1.47 11.70 34.65 −4.87 14.40 30.02 −14.92 17.74 1.50 29.93 −7.79 5.47 27.64 −11.84 8.07 24.33 −24.73 11.76 1.75 20.57 −14.34 −1.03 20.06 −18.97 1.47 18.27 −34.93 5.50 2.00 10.09 −21.09 −7.82 11.87 −26.23 −5.41 11.80 −45.49 −1.05 2.25 −1.72 −28.06 −14.93 2.97 −33.66 −12.64 4.87 −56.37 −7.95 2.50 −15.23 −35.20 −22.40 −6.78 −41.29 −20.26 −2.61 −67.59 −15.22 2.75 −31.14 −42.59 −30.42 −17.68 −49.10 −28.42 −10.77 −79.34 −23.00 3.00 −51.01 −50.46 −39.34 −30.39 −57.42 −37.45 −19.98 −92.22 −31.57 A greater awareness of users about the need to establish adaptive limits without tolerance in the use of HVAC systems would therefore ensure both a more sustainable energy performance of buildings and acceptable thermal conditions inside them according to the existing standards of adaptive thermal comfort. However, presumably the possible energy savings achieved with this strategy can be increased by using natural ventilation. In this regard, one of the limitations of the study is that the maintenance of comfort hours is based on the use of HVAC systems. The combined use of adaptive setpoint temperatures with natural ventilation would imply higher savings in the energy consumption of residential buildings. Therefore, the combination of natural ventilation and adaptive setpoint temperatures should be studied in future research studies. Appl. Sci. 2020, 10, x FOR PEER REVIEW 18 of 23 Figure 13. Average increase percentage in the energy consumption due to the improvement in the user’s expectations in 0.25 °C in 2050 and 2100. 4. Conclusions This paper analyzed the influence of the improvement in users’ thermal expectation levels by using adaptive setpoint temperatures. The analysis was based on the category for new buildings included in EN 16798-1:2019 and was conducted in an international context by analyzing the main cities of four countries of southern Europe and in three different climate scenarios. The results based on 4116 simulations showed the following aspects: - The use of adaptive thermal comfort models with a tolerance of 0.00 °C led to significant energy consumption savings with respect to a highly effective static model. The improvement in users’ expectation level implied that, from the narrowing of the comfort zone in 3 °C (i.e., applying the model with a tolerance of 1.50 °C), there were no savings in the energy consumption with respect to the static model. However, this tendency was different according to the type of consumption analyzed, demonstrating that the cooling energy consumption had a greater possibility of tolerance. This aspect would imply that, in certain moments, users do not need to set the internal spaces with the linear correlations from EN 16798-1:2019 when the running mean outdoor temperature is near or greater than 30 °C. - The application of strategies of adaptive setpoint temperatures for new buildings obtained energy savings greater than 1000 kWh/year in most cities analyzed. Furthermore, there were similar energy-saving tendencies among the countries which were near each other. In this regard, the energy saving was similar between Greece and Italy, and between Spain and Portugal. Spain was the country which was characterized by presenting the greatest and the lowest energy-saving values due to the huge variety of existing climate typologies in the countries, some of which were characterized by a minimum energy demand with the static model. - The progressive improvement in users’ thermal expectations in 0.25 °C implied a rise with respect to the energy consumption obtained in the previous tolerance level between 6.57 and 9.31% in all the scenarios analyzed. - In future climate change scenarios, the rise in external temperatures meant that the saving in cooling degrees with respect to the static model increased, thus implying that the maximum tolerance, from which an energy saving was obtained with respect to the static model, increased from 1.50 °C of the current scenario to 1.75 °C of future scenarios. This aspect is useful to corroborate the possibilities of using a less demanding upper limit when average external temperatures are near or higher than 30 °C. Figure 13. Average increase percentage in the energy consumption due to the improvement in the user’s expectations in 0.25 ◦C in 2050 and 2100. Appl. Sci. 2020,10, 5282 18 of 22 4. Conclusions This paper analyzed the influence of the improvement in users’ thermal expectation levels by using adaptive setpoint temperatures. The analysis was based on the category for new buildings included in EN 16798-1:2019 and was conducted in an international context by analyzing the main cities of four countries of southern Europe and in three different climate scenarios. The results based on 4116 simulations showed the following aspects: - The use of adaptive thermal comfort models with a tolerance of 0.00 ◦ C led to significant energy consumption savings with respect to a highly effective static model. The improvement in users’ expectation level implied that, from the narrowing of the comfort zone in 3 ◦ C (i.e., applying the model with a tolerance of 1.50 ◦ C), there were no savings in the energy consumption with respect to the static model. However, this tendency was different according to the type of consumption analyzed, demonstrating that the cooling energy consumption had a greater possibility of tolerance. This aspect would imply that, in certain moments, users do not need to set the internal spaces with the linear correlations from EN 16798-1:2019 when the running mean outdoor temperature is near or greater than 30 ◦C. - The application of strategies of adaptive setpoint temperatures for new buildings obtained energy savings greater than 1000 kWh/year in most cities analyzed. Furthermore, there were similar energy-saving tendencies among the countries which were near each other. In this regard, the energy saving was similar between Greece and Italy, and between Spain and Portugal. Spain was the country which was characterized by presenting the greatest and the lowest energy-saving values due to the huge variety of existing climate typologies in the countries, some of which were characterized by a minimum energy demand with the static model. - The progressive improvement in users’ thermal expectations in 0.25 ◦ C implied a rise with respect to the energy consumption obtained in the previous tolerance level between 6.57 and 9.31% in all the scenarios analyzed. - In future climate change scenarios, the rise in external temperatures meant that the saving in cooling degrees with respect to the static model increased, thus implying that the maximum tolerance, from which an energy saving was obtained with respect to the static model, increased from 1.50 ◦ C of the current scenario to 1.75 ◦ C of future scenarios. This aspect is useful to corroborate the possibilities of using a less demanding upper limit when average external temperatures are near or higher than 30 ◦C. To conclude, the results of this research give greater knowledge about the possibilities of using adaptive setpoint temperatures and the possible impact the improvement in users’ thermal expectations. The research results may provide an opportunity for architects or engineers to establish operational patterns of the most efficient HVAC systems. Furthermore, local governments can design user awareness campaigns to recommend a more appropriate use of HVAC systems by family units. Due to the possible influence of users, further steps of this research will be focused on performing actual monitoring of users using adaptive setpoint temperatures. In addition, the analysis of the combination of adaptive setpoint temperatures and natural ventilation would imply an adaptive strategy framework for mixed-mode buildings. Finally, the case studies from other continents or regions (e.g., United States of America or China) should be analyzed in future works. Author Contributions: Conceptualization, methodology, investigation, writing—original draft preparation, and editing and visualization, D.B.-H., D.S.-G., C.R.-B. and J.A.P.-A. All authors have read and agreed to the published version of the manuscript. Funding: This research received no external funding. Conflicts of Interest: The authors declare no conflict of interest. Appl. Sci. 2020,10, 5282 19 of 22 Nomenclature A2 climate change scenario ASHRAE American Society of Heating Refrigerating and Air-Conditioning Engineers COP Coefficient of Performance EER Energy Efficiency Ratio EPW EnergyPlus Weather HVAC Heating, Ventilation, and Air Conditioning SHGC Solar Heat Gain Coefficient Text,day daily mean external temperature [◦C] Trm running mean outdoor temperature [◦C] VRF Variable Refrigerant Flow References 1. European Commission. A Roadmap for Moving to a Competitive Low Carbon Economy in 2050; European Commission: Brussels, Belgium, 2011; pp. 1–15. 2. Intergovernmental Panel on Climate Change (Ed.) Climate Change 2014: Synthesis Report. Contribution of Working Groups I, II and III to the Fifth Assessment Report of the Intergovernmental Panel on Climate Change; Cambridge University Press: Cambridge, UK, 2014. 3. Bienvenido-Huertas, D.; P é rez-Fargallo, A.; Alvarado-Amador, R.; Rubio-Bellido, C. Influence of climate on the creation of multilayer perceptrons to analyse the risk of fuel poverty. Energy Build. 2019 ,198, 38–60. [CrossRef] 4. P é rez-Fargallo, A.; Rubio-Bellido, C.; Pulido-Arcas, J.A.; Trebilcock, M. Development policy in social housing allocation: Fuel poverty potential risk index. Indoor Built Environ. 2017,26, 980–998. [CrossRef] 5. Castaño-Rosa, R.; Sol í s-Guzm á n, J.; Marrero, M. A novel Index of Vulnerable Homes: Findings from application in Spain. Indoor Built Environ. 2020,29, 311–330. [CrossRef] 6. Liddell, C.; Morris, C.; Thomson, H.; Guiney, C. Excess winter deaths in 30 European countries 1980–2013: A critical review of methods. J. Public Health 2016,38, 806–814. [CrossRef] 7. Teller-Elsberg, J.; Sovacool, B.; Smith, T.; Laine, E. Fuel poverty, excess winter deaths, and energy costs in Vermont: Burdensome for whom? Energy Policy 2016,90, 81–91. [CrossRef] 8. Kurekci, N.A. Determination of optimum insulation thickness for building walls by using heating and cooling degree-day values of all Turkey’s provincial centers. Energy Build. 2016,118, 197–213. [CrossRef] 9. Vine, E.L.; Kazakevicius, E. Residential energy use in Lithuania: The prospects for energy efficiency. Energy 1999,24, 591–603. [CrossRef] 10. Au-Yong, C.P.; Ali, A.S.; Ahmad, F. Improving occupants’ satisfaction with effective maintenance management of HVAC system in office buildings. Autom. Constr. 2014,43, 31–37. [CrossRef] 11. Cho, J.; Kim, Y.; Koo, J.; Park, W. Energy-cost analysis of HVAC system for office buildings: Development of a multiple prediction methodology for HVAC system cost estimation. Energy Build. 2018 ,173, 562–576. [CrossRef] 12. Echarri, V. Thermal ceramic panels and passive systems in mediterranean housing: Energy savings and environmental impacts. Sustainability 2017,9, 1613. [CrossRef] 13. Aksoy, U.T.; Inalli, M. Impacts of some building passive design parameters on heating demand for a cold region. Build. Environ. 2006,41, 1742–1754. [CrossRef] 14. Invidiata, A.; Lavagna, M.; Ghisi, E. Selecting design strategies using multi-criteria decision making to improve the sustainability of buildings. Build. Environ. 2018,139, 58–68. [CrossRef] 15. Stern, P.C.; Janda, K.B.; Brown, M.A.; Steg, L.; Vine, E.L.; Lutzenhiser, L. Opportunities and insights for reducing fossil fuel consumption by households and organizations. Nat. Energy 2016,1, 16043. [CrossRef] 16. Echarri-Iribarren, V.; Rizo-Maestre, C.; Sanjuan-Palermo, J.L. Underfloor heating using ceramic thermal panels and solar thermal panels in public buildings in the Mediterranean: Energy savings and healthy indoor environment. Appl. Sci. 2019,9, 2089. [CrossRef] 17. Ruth, C.E.; Byrne, R.; Hewitt, N.J.; MacArtain, P. Electricity autoproduction, storage and billing: A case study at Dundalk Institute of Technology, Ireland. Sustain. Energy Technol. Assess. 2019,35, 257–264. [CrossRef] Appl. Sci. 2020,10, 5282 20 of 22 18. Allouhi, A.; El Fouih, Y.; Kousksou, T.; Jamil, A.; Zeraouli, Y.; Mourad, Y. Energy consumption and efficiency in buildings: Current status and future trends. J. Clean. Prod. 2015,109, 118–130. [CrossRef] 19. Ueno, T.; Sano, F.; Saeki, O.; Tsuji, K. Effectiveness of an energy-consumption information system on energy savings in residential houses based on monitored data. Appl. Energy 2006,83, 166–183. [CrossRef] 20. Papadopoulos, S.; Kontokosta, C.E.; Vlachokostas, A.; Azar, E. Rethinking HVAC temperature setpoints in commercial buildings: The potential for zero-cost energy savings and comfort improvement in different climates. Build. Environ. 2019,155, 350–359. [CrossRef] 21. Parkinson, T.; de Dear, R.; Brager, G. Nudging the adaptive thermal comfort model. Energy Build. 2020 , 206, 109559. [CrossRef] 22. Ren, Z.; Chen, D. Modelling study of the impact of thermal comfort criteria on housing energy use in Australia. Appl. Energy 2018,210, 152–166. [CrossRef] 23. Lakeridou, M.; Ucci, M.; Marmot, A.; Ridley, I. The potential of increasing cooling set-points in air-conditioned offices in the UK. Appl. Energy 2012,94, 338–348. [CrossRef] 24. Hoyt, T.; Arens, E.; Zhang, H. Extending air temperature setpoints: Simulated energy savings and design considerations for new and retrofit buildings. Build. Environ. 2014,88, 89–96. [CrossRef] 25. Spyropoulos, G.N.; Balaras, C.A. Energy consumption and the potential of energy savings in Hellenic office buildings used as bank branches—A case study. Energy Build. 2011,43, 770–778. [CrossRef] 26. Fernandez, N.; Katipamula, S.; Wang, W.; Huang, Y.; Liu, G. Energy savings modelling of re-tuning energy conservation measures in large office buildings. J. Build. Perform. Simul. 2015,8, 391–407. [CrossRef] 27. Parry, M.L.; Canziani, O.F.; Palutikof, J.P.; van der Linden, P.J.; Hanson, C.E. Contribution of Working Group II to the Fourth Assessment Report of the Intergovernmental Panel on Climate Change; Cambridge University Press: Cambridge, UK, 2007. 28. Saidur, R. Energy consumption, energy savings, and emission analysis in Malaysian office buildings. Energy Policy 2009,37, 4104–4113. [CrossRef] 29. Yamtraipat, N.; Khedari, J.; Hirunlabh, J.; Kunchornrat, J. Assessment of Thailand indoor set-point impact on energy consumption and environment. Energy Policy 2006,34, 765–770. [CrossRef] 30. Moon, J.W.; Han, S.H. Thermostat strategies impact on energy consumption in residential buildings. Energy Build. 2011,43, 338–346. [CrossRef] 31. Mishra, A.K.; Ramgopal, M. Field studies on human thermal comfort—An overview. Build. Environ. 2013 , 64, 94–106. [CrossRef] 32. Van Hoof, J. Forty years of Fanger’s model of thermal comfort: Comfort for all? Indoor Air 2008 ,18, 182–201. [CrossRef] 33. Rupp, R.F.; V á squez, N.G.; Lamberts, R. A review of human thermal comfort in the built environment. Energy Build. 2015,105, 178–205. [CrossRef] 34. Nicol, J.F.; Humphreys, M.A. Adaptive thermal comfort and sustainable thermal standards for buildings. Energy Build. 2002,34, 563–572. [CrossRef] 35. Wong, N.H.; Feriadi, H.; Lim, P.Y.; Tham, K.W.; Sekhar, C.; Cheong, K.W. Thermal comfort evaluation of naturally ventilated public housing in Singapore. Build. Environ. 2002,37, 1267–1277. [CrossRef] 36. Ye, X.J.; Zhou, Z.P.; Lian, Z.W.; Liu, H.M.; Li, C.Z.; Liu, Y.M. Field study of a thermal environment and adaptive model in Shanghai. Indoor Air 2006,16, 320–326. [CrossRef] 37. van der Linden, A.C.; Boerstra, A.C.; Raue, A.K.; Kurvers, S.R.; De Dear, R.J. Adaptive temperature limits: A new guideline in the Netherlands: A new approach for the assessment of building performance with respect to thermal indoor climate. Energy Build. 2006,38, 8–17. [CrossRef] 38. Boerstra, A.C.; van Hoof, J.; van Weele, A.M. A new hybrid thermal comfort guideline for the Netherlands: Background and development. Archit. Sci. Rev. 2015,58, 24–34. [CrossRef] 39. Yun, G.Y.; Lee, J.H.; Steemers, K. Extending the applicability of the adaptive comfort model to the control of air-conditioning systems. Build. Environ. 2016,105, 13–23. [CrossRef] 40. S á nchez-Guevara S á nchez, C.; Mavrogianni, A.; Neila Gonz á lez, F.J. On the minimal thermal habitability conditions in low income dwellings in Spain for a new definition of fuel poverty. Build. Environ. 2017 ,114, 344–356. [CrossRef] 41. American Society of Heating Refrigerating and Air Conditioning Engineers. ASHRAE Standard 55-2017 Thermal Environmental Conditions for Human Occupancy; American Society of Heating Refrigerating and Air Conditioning Engineers: Atlanta, GA, USA, 2017. Appl. Sci. 2020,10, 5282 21 of 22 42. S á nchez-Garc í a, D.; Bienvenido-Huertas, D.; Tristancho-Carvajal, M.; Rubio-Bellido, C. Adaptive Comfort Control Implemented Model (ACCIM) for Energy Consumption Predictions in Dwellings under Current and Future Climate Conditions: A Case Study Located in Spain. Energies 2019,12, 1498. [CrossRef] 43. Wang, C.; Pattawi, K.; Lee, H. Energy saving impact of occupancy-driven thermostat for residential buildings. Energy Build. 2020,211, 109791. [CrossRef] 44. Bienvenido-Huertas, D.; S á nchez-Garc í a, D.; P é rez-Fargallo, A.; Rubio-Bellido, C. Optimization of energy saving with adaptive setpoint temperatures by calculating the prevailing mean outdoor air temperature. Build. Environ. 2020,170, 106612. [CrossRef] 45. Luo, M.; Wang, Z.; Brager, G.; Cao, B.; Zhu, Y. Indoor climate experience, migration, and thermal comfort expectation in buildings. Build. Environ. 2018,141, 262–272. [CrossRef] 46. European Committee for Standardization. EN 15251:2007 Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Quality, Thermal Environment, Lighting and Acoustics; European Committee for Standardization: Brussels, Belgium, 2007. 47. European Committee for Standardization. EN 16798-1:2019 Energy Performance of Buildings—Ventilation for Buildings—Part 1: Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acous; European Committee for Standardization: Brussels, Belgium, 2019. 48. S á nchez-Garc í a, D.; Rubio-Bellido, C.; Tristancho, M.; Marrero, M. A comparative study on energy demand through the adaptive thermal comfort approach considering climate change in office buildings of Spain. Build. Simul. 2020,13, 51–63. [CrossRef] 49. Bienvenido-Huertas, D.; Rubio-Bellido, C.; P é rez-Fargallo, A.; Pulido-Arcas, J.A. Energy saving potential in current and future world built environments based on the adaptive comfort approach. J. Clean. Prod. 2020 , 249, 119306. [CrossRef] 50. Mi, Z.; Guan, D.; Liu, Z.; Liu, J.; Vigui é , V.; Fromer, N.; Wang, Y. Cities: The core of climate change mitigation. J. Clean. Prod. 2019,207, 582–589. [CrossRef] 51. Marvuglia, A.; Havinga, L.; Heidrich, O.; Fonseca, J.; Gaitani, N.; Reckien, D. Advances and challenges in assessing urban sustainability: An advanced bibliometric review. Renew. Sustain. Energy Rev. 2020 , 124, 109788. [CrossRef] 52. Hellenic Parliament. N. 3852/2010, New Architecture of Local Government and Decentralized Administration-Kallikratis Program; Hellenic Parliament: Athens, Greece, 2010. 53. METEONORM. Handbook Part II: Theory (Version 7.3.1); METEONORM: Bern, Switzerland, 2019. 54. Naki´cenovi´c, N.; Swart, R. Special Report on Emissions Scenarios. A Special Report of Working Group III of the Intergovernmental Panel on Climate Change; Cambridge University Press: Cambridge, UK, 2000; ISBN 0 521 80081 1. 55. Nematchoua, M.K.; Orosa, J.A.; Reiter, S. Climate change: Variabilities, vulnerabilities and adaptation analysis—A case of seven cities located in seven countries of Central Africa. Urban Clim. 2019 ,29, 100486. [CrossRef] 56. Verichev, K.; Zamorano, M.; Carpio, M. Effects of climate change on variations in climatic zones and heating energy consumption of residential buildings in the southern Chile. Energy Build. 2020 ,215, 109874. [CrossRef] 57. Ciancio, V.; Salata, F.; Falasca, S.; Curci, G.; Golasi, I.; de Wilde, P. Energy demands of buildings in the framework of climate change: An investigation across Europe. Sustain. Cities Soc. 2020, 154244. [CrossRef] 58. Roetzel, A.; Tsangrassoulis, A.; Dietrich, U. Impact of building design and occupancy on office comfort and energy performance in different climates. Build. Environ. 2014,71, 165–175. [CrossRef] 59. Mourshed, M. The impact of the projected changes in temperature on heating and cooling requirements in buildings in Dhaka, Bangladesh. Appl. Energy 2011,88, 3737–3746. [CrossRef] 60. Invidiata, A.; Ghisi, E. Impact of climate change on heating and cooling energy demand in houses in Brazil. Energy Build. 2016,130, 20–32. [CrossRef] 61. Triana, M.A.; Lamberts, R.; Sassi, P. Should we consider climate change for Brazilian social housing? Assessment of energy efficiency adaptation measures. Energy Build. 2018,158, 1379–1392. [CrossRef] 62. Shen, P.; Lior, N. Vulnerability to climate change impacts of present renewable energy systems designed for achieving net-zero energy buildings. Energy 2016,114, 1288–1305. [CrossRef] 63. Shen, P. Impacts of climate change on U.S. building energy use by using downscaled hourly future weather data. Energy Build. 2017,134, 61–70. [CrossRef] Appl. Sci. 2020,10, 5282 22 of 22 64. Robert, A.; Kummert, M. Designing net-zero energy buildings for the future climate, not for the past. Build. Environ. 2012,55, 150–158. [CrossRef] 65. Bienvenido-Huertas, D.; Oliveira, M.; Rubio-Bellido, C.; Mar í n, D. A Comparative Analysis of the International Regulation of Thermal Properties in Building Envelope. Sustainability 2019,11, 5574. [CrossRef] 66. Grazieschi, G.; Gori, P.; Lombardi, L.; Asdrubali, F. Life cycle energy minimization of autonomous buildings. J. Build. Eng. 2020,30, 101229. [CrossRef] 67. Rossi, M.; Rocco, V.M. External walls design: The role of periodic thermal transmittance and internal areal heat capacity. Energy Build. 2014,68, 732–740. [CrossRef] 68. Rodrigues, E.; Fernandes, M.S.; Gaspar, A.R.; Gomes, Á .; Costa, J.J. Thermal transmittance effect on energy consumption of Mediterranean buildings with different thermal mass. Appl. Energy 2019 ,252, 113437. [CrossRef] 69. Fernandes, M.S.; Rodrigues, E.; Gaspar, A.R.; Costa, J.J.; Gomes, Á . The impact of thermal transmittance variation on building design in the Mediterranean region. Appl. Energy 2019,239, 581–597. [CrossRef] 70. Jiru, T.E. Combining HVAC energy conservation measures to achieve energy savings over standard requirements. Energy Build. 2014,73, 171–175. [CrossRef] 71. Abediniangerabi, B.; Shahandashti, S.M.; Bell, B.; Chao, S.H.; Makhmalbaf, A. Building energy performance analysis of ultra-high-performance fiber-reinforced concrete (UHP-FRC) façade systems. Energy Build. 2018 , 174, 262–275. [CrossRef] 72. Kim, D.; Cox, S.J.; Cho, H.; Im, P. Evaluation of energy savings potential of variable refrigerant flow (VRF) from variable air volume (VAV) in the U.S. climate locations. Energy Rep. 2017,3, 85–93. [CrossRef] 73. O’Neill, Z.; Niu, F. Uncertainty and sensitivity analysis of spatio-temporal occupant behaviors on residential building energy usage utilizing Karhunen-Loève expansion. Build. Environ. 2017,115, 157–172. [CrossRef] 74. Shishegar, N.; Boubekri, M. Quantifying electrical energy savings in offices through installing daylight responsive control systems in hot climates. Energy Build. 2017,153, 87–98. [CrossRef] 75. Sardoueinasab, Z.; Yin, P.; O’Neal, D. Energy modeling and analysis of inherent air leakage from parallel fan-powered terminal units using EMS in EnergyPlus. Energy Build. 2018,176, 109–119. [CrossRef] © 2020 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).